Weil-McLain boiler error codes, lockouts and how to reset

232 codes for 40 model series, each with the wording and source from Weil-McLain boiler manuals, control supplements and user's manuals.

How House Works EditorialChecked against 65 sources,
How it is checked
Methodology
Page
HHW · ERROR-CODES · WEIL-MCLAIN
Based on
Weil-McLain boiler manuals, control supplements and user's manuals

Meanings are quoted from Weil-McLain boiler manuals, control supplements and user's manuals. The "Who" column is our reading of the remedy in those documents: whether an owner can do the first checks, or the fix belongs to a licensed technician.

Codes with step-by-step checks

  • E02Ignition failed after 5 tries
  • E03Ignition or gas valve electrical problem
  • E04Power lost after lockout
  • E05Internal control or display error
  • E18Outlet water above 210°F
  • E28Blower not running
  • E37Return sensor open circuit
  • Status 3Burner on for space heating
  • Status 6Burner off, temperature reached
  • A01No burner ignition

All Weil-McLain codes

CodeMeaningWhoSeriesSource
E00“Flame detected on start-up”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 28; Ultra Series 1 Boiler Manual p. 41
E02“Igntion failed after 5 retries”
What to check
TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E02“Ignition failed through 5 attempts: NO SPARK OCCURS:”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 28
E02“Ignition failed through 5 attempts: Spark occurs, but no flame:”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 28
E02“Ignition failed through 5 attempts: Flame occurs, but flame signal strength is low ( less than 4 vdc between low voltage terminal strip terminal 9 and ground):”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 29
E03“Ignition failure or gas valve electrical problem”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 29
E03“Internal control failure (see Troubleshooting)”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E03“Internal control failure”
What to check
TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E04“Voltage lost after lockout occurred or AC voltage fluctuations on incoming power”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E04“Power lost after lockout (see Troubleshooting)”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E04“Power lost after lockout”
What to check
TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E05“Internal Control or Display error”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E05“See Troubleshooting”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E05“Internal control failure”
What to check
TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E06“Internal Control Failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 30; Ultra Series 1 Boiler Manual p. 41
E06“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E07“Gas valve relay error”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E07“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E07“Internal control failure”TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E08“Internal Control Failure”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E09“Internal Control Failure”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E11“EEPROM Error”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E11“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E11“Internal control error”TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E12“External limit open (limit wired in hard lockout circuit)”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E12“External limit open (between terminal 6 and 8)”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E13“Usually indicates a sensor problem”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E13“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E13“Internal control failure”TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E14“Supply water sensor problem”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 30
E14“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E14“Internal control failure”TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E15“Internal control failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 30; Ultra Series 1 Boiler Manual p. 41
E15“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E16“Internal control failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 30; Ultra Series 1 Boiler Manual p. 41
E16“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E17“Internal control failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 30; Ultra Series 1 Boiler Manual p. 41
E17“See Troubleshooting”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E18“Outlet water temperature was higher than 210°F”
What to check
TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E18“Thermal overrun condition – Outlet water temperature above 210 °F.”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 31
E19“Return water temperature was higher than 210°F”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E19“Thermal overrun condition – Return water temperature above 210 °F.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 31
E25“Temperature rise > 58°F”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 31
E25“Temperature rise too high (> 58°F)”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 21
E25“Outlet temperature increased too fast”TechnicianUltra Series 1 (older manual)Ultra Series 1 Boiler Manual p. 41
E28“No signal from blower”
What to check
Printed beside the row in the control supplement (p. 21): “Check INFO #6”.
TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E28“Blower not running”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 31
E29“Blower signal not zero when it should be”
Printed beside the row in the control supplement (p. 21): “Check INFO #6”.
TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 31; Ultra Series 1 Boiler Manual p. 41
E30“Temperature rise across boiler over 58 °F, and occurred 20 times.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E31“Outlet temperature sensor short circuit”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E31“Outlet water temperature sensor short circuit.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E32“Return temperature sensor short circuit”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E32“Return water temperature sensor short circuit.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E36“Outlet temperature sensor open circuit”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E36“Outlet water temperature sensor open circuit.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E37“Return temperature sensor open circuit”
What to check
TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E37“Return water temperature sensor open circuit.”
What to check
TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E44“Internal control failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 32; Ultra Series 1 Boiler Manual p. 41
E52“Flue temperature was higher than 225°F”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E52“Flue temperature exceeded 225 °F.”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E60“Internal error reading parameters”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E60“Internal control failure”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E61“Air flow circuit failure”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E61“Internal control failure”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
E65“Not enough blower driving force”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 21; Ultra Series 1 Boiler Manual p. 41
E65“Blower signal too low (not enough driving force)”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 32
b18“Outlet temperature too high (over 203°F) — Burner off until outlet water temp drops 9°F below target temperature”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b18“High limit operation — burner off until outlet water temp drops below 203 °F minus the ON differential”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 26
b19“Return temperature too high (over 203°F) — Burner off until both outlet and return water temperatures drop 9°F below target temperature”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b19“Return water temperature higher than 203 °F. — burner off until return water temp drops below 203 °F minus the ON differential”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 26
b24“Return temp higher than supply temp — Burner off waiting for correction”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b24“Return temp higher than supply temp — Burner off waiting for supply temp to rise above return temp”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 26
b25“Outlet water temp rose too quickly — Burner off for 10 minute wait (burner recycles, increasing wait 1 minute each attempt, to max. of 15 minutes)”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b25“Outlet water temp rose too quickly — burner off for 10 minute wait (burner recycles, increasing wait 1 minute each attempt, to a max of 15 minutes)”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 27
b26“External limit open on limit wired in soft lockout (auto reset) circuit — Burner off for 150 seconds”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b26“External limit open on limit wired in soft lockout circuit (auto reset). Low voltage terminals 6 and 7. Burner off for 150 seconds”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 27
b29“Blower signal not zero when it should be — Burner off until signal condition terminates”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b29“Blower signal not zero when it should be — Burner off until signal condition corrected”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 27
b30“Temperature rise across boiler more than 58°F — Burner off for 150 second wait (plus 1 additional minute for each failed attempt, up to max. of 22 minutes each time)”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
b30“Temperature rise across boiler more than 45°F. — Burner off for 150 second wait (plus 1 additional minute for each failed attempt, up to 20 times, then hard lockout occurs”TechnicianUltra Series 1 & 2Ultra Gas Series 2 Control Supplement p. 27
b35“Short circuit across flue temperature sensor terminals — Burner off until corrected”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 27; Ultra Series 1 Boiler Manual p. 38
b40“Open circuit across flue temperature sensor terminals — Burner off until corrected”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 27; Ultra Series 1 Boiler Manual p. 38
b52“Flue temperature exceeded 216°F, but did not exceed 225°F (hard lockout occurs above 225°F) — Burner off for 150 second wait”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 27; Ultra Series 1 Boiler Manual p. 38
b65“Waiting for blower to start”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 27; Ultra Series 1 Boiler Manual p. 38
Status 0“Standby — no call for heat”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 1“Pre-purge (10 seconds) or Post-purge (15 seconds)”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 2“Ignition”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 3“Burner on for space heating”
What to check
Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 4“Burner on for DHW heating”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 5“Checking airflow before prepurge”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 6“Burner off because temperature setting has been reached”
What to check
Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 7“Pump on after space heating cycle for run-on of 10 seconds”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status 8“Pump on after DHW heating cycle for run-on of 30 seconds”Owner can checkUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
A01“No burner ignition after five attempts”
What to check
TechnicianAquaBalance Series 2AquaBalance Series 2 Boiler Manual p. 92
A01“Lockout indication”
What to check
TechnicianAquaBalance (Series 1)AquaBalance Boiler Manual p. 88
A02“False flame indication”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A03“High limit protection: pump does not run or no water circulation”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A04“F07 repeated 3 times in the last 24 hours”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A05“No frequency feedback from fan after 1 hour”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A06“6 times flame loss in 4 minutes time frame”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A16“Outside sensor is not connected”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A23“Nominal water pressure not reached within maximum allowed time”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A24“More than 3 water fillings in 24 hours”TechnicianAquaBalance (Series 1)AquaBalance Boiler Manual p. 88
A26“F40 repeated 3 times in the last hour”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A41“Temperature sensor not or bad connected to the pipe (CH mode)”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A42“Too high difference between two CH supply water temperature sensors”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A44“Temperature sensor not or bad connected to the pipe (DHW mode)”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A61“Flame circuit error”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A62“Gas valve circuit”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A63“E2 prom error”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
A65“ADC circuit error”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 88; AquaBalance Series 2 Boiler Manual p. 92
F07“The Exhaust gases temperature is too high.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F10“The CH supply water temperature sensor 1 error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F11“The CH return water temperature sensor error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F12“The DHW water temperature sensor error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F13“The Exhaust gases temperature sensor error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F14“The CH supply water temperature sensor 2 error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F15“Minimum and maximum frequency feedback from fan error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F20“The water pressure in the CH installation is near the low level.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F21“The water pressure in the CH installation is near the high level.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F27“The exhaust gas temperature is too high (PVC/CPVC/Polypro/AL29-4C - selection).”TechnicianAquaBalance Series 2AquaBalance Series 2 Boiler Manual p. 95
F27“The exhaust gas temperature is too high (PVC/CPVC selection).”TechnicianAquaBalance (Series 1)AquaBalance Boiler Manual p. 91
F34“Low mains voltage.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F35“Frequency error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F37“The water pressure in the CH installation is too low.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F39“Outside sensor error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F40“The water pressure in the CH installation is too high or there's a Control fault.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F43“Heat exchanger protection.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F47“Water pressure sensor not connected.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F50“Variable input switch contact opened.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F51“Low water error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F52“Too high difference between two CH supply water temperature sensors.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F53“High limit thermostat input error.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F64“5 MicroCom reset in 15 minutes time frame.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
F66“Software doesn't match.”TechnicianAquaBalance (Series 1), AquaBalance Series 2AquaBalance Boiler Manual p. 91; AquaBalance Series 2 Boiler Manual p. 95
D1“After cycle of Domestic water mode, D1 will be displayed.”Owner can checkAquaBalance (Series 1), AquaBalance Series 2, AquaBalance Series 1 & 2AquaBalance Boiler Manual p. 106; AquaBalance Series 2 Boiler Manual p. 68; AquaBalance Control Module Quick Start Guide p. 13
D2“When required boiler water set - point is reached D2 will be displayed.”Owner can checkAquaBalance (Series 1), AquaBalance Series 2, AquaBalance Series 1 & 2AquaBalance Boiler Manual p. 106; AquaBalance Series 2 Boiler Manual p. 68; AquaBalance Control Module Quick Start Guide p. 13
D3“After an attempt for ignition, re-trial ignition delay is in effect (D3 is displayed).”TechnicianAquaBalance (Series 1), AquaBalance Series 2, AquaBalance Series 1 & 2AquaBalance Boiler Manual p. 106; AquaBalance Series 2 Boiler Manual p. 68; AquaBalance Control Module Quick Start Guide p. 13
60F > RETURN“Occurs if either Boiler Out temperatures are greater than Boiler In temperature by more than 60F or the burner has been on for less than 2 minutes. If this condition occurs when the burner has been on for more than 2 minutes, the burner stops firing but no message or lockout occurs.”TechnicianSimplicitySimplicity Boiler Manual p. 145
A2D FAULT“The analog reading of the internal voltage reference on U1 read out of range 2 times in a row.”TechnicianSimplicitySimplicity Boiler Manual p. 146
AIR P-SW OPEN“Occurs when Air Pressure connection is open.”TechnicianSimplicitySimplicity Boiler Manual p. 144
AIR PRESSURE SW FAULT“Air Pressure switch is open”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
ALL LED’S FLASHING“Failure to establish pilot flame after 4 attempts.”Technician
6 seriesEG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
6 documentsEG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
ALL LED’S FLASHING“Failure to establish pilot flame after 4 attempts. Propane requires Manual Reset, see pages 34 and 35.”TechnicianCGa Series 2CGa Boiler Manual Series 2 p. 49
ALL LED’S FLASHING (Propane Gas Only)“Failure to establish pilot flame after 4 attempts. Follow Manual Reset Procedure on pages 34 & 35 to correct.”TechnicianCGa Series 2CGA Series 2 Boiler Manual p. 49
AUTO LIMIT“Auto Limit chain / electrical circuit is open.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 64; CGi Series 5 Boiler Manual p. 76; EG Series 7 Boiler Manual p. 74
BLOWER FAULT“Blower unable to reach required speed or does not reach 0 RPM when turned off.”Technician
5 seriesEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, Ultra Series 3 (CT), Ultra Series 4
5 documentsEvergreen Series 1 Boiler p. 113; Evergreen Boiler Manual for Sizes 110-155 p. 110; Evergreen Boiler Manual for Sizes 220-399 p. 108; Ultra Series 3-CT Boiler Manual p. 106; Ultra Series 4 Boiler Manual p. 122
BLOWER FAULT“Blower unable to reach required speed or does not reach 0 RPM when turned off. NOTICE: ECO 70 or 110 only — The blower will not rotate without a low voltage signal. Unplugging the low voltage blower wire harness will not allow or cause the blower to rotate.”TechnicianECO (no series number on cover), ECO Series 2ECO Boiler Manual Series 1 p. 96; ECO Series 2 Boiler Manual p. 101
BLOWER FAULT“Blower unable to reach required speed or does not reach 0 RPM when turned off. NOTICE: WM97+70 only — The blower will not rotate without a low voltage signal. Unplugging the low voltage blower wire harness will not allow or cause the boiler to rotate.”TechnicianWM97+ Series 2WM97+ Series 2 Boiler Manual p. 115
BLOWER FAULT“Blower unable to reach required speed or does not reach 0 RPM when turned off. NOTICE: WM97+70 or 110 only — The blower will not rotate without a low voltage signal. Unplugging the low voltage blower wire harness will not allow or cause the boiler to rotate.”TechnicianWM97+ (no series number on cover)WM97+ CT Boiler Manual Series 1 p. 109
BLOWER FAULT 1“Blower does not reach zero RPM within 4 minutes when mode is Standby or Prepump.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BLOWER FAULT 2“Blower unable to reach required pre-purge speed or ignition speed. Blower failed to complete calibration within 4 minutes.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BLOWER FAULT 3“Blower is outside of minimum or maximum speed for 10 seconds while burner is firing.”TechnicianSimplicitySimplicity Boiler Manual p. 146
BLOWER FAULT 4“Blower drops to zero RPM while burner is firing.”TechnicianSimplicitySimplicity Boiler Manual p. 146
BOILER IN OPEN“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BOILER IN SHORT“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BOILER OUT 10F“The Boiler Control measures a difference greater than 10F between Boiler Out 1 & 2.”TechnicianCGi Series 5CGi Series 5 Boiler Manual p. 78
BOILER OUT OPEN“Boiler Control measures an open circuit.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
BOILER OUT SHORT“Boiler Control measures a closed circuit with no resistance.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
BOILER OUT1 OPEN“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BOILER OUT1 SHRT“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BOILER OUT2 OPEN“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
BOILER OUT2 SHRT“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
CALIBRATE IS ACTIVE“Occurs when blower calibration is underway.”TechnicianSimplicitySimplicity Boiler Manual p. 148
CALIBRATE NEEDED“Occurs when the boiler's blower motor has not yet undergone calibration.”TechnicianSimplicitySimplicity Boiler Manual p. 148
CH VOLTAGE HIGH“CH / Thermostat1 input excessive voltage.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 67; CGi Series 5 Boiler Manual p. 79; EG Series 7 Boiler Manual p. 77
CHIP FAULT“Occurs when the internal clock of the control is out of sync.”TechnicianSimplicitySimplicity Boiler Manual p. 145
CLOCK FAULT“When the real time clock chip is unable to be read.”TechnicianSimplicitySimplicity Boiler Manual p. 148
CLOSURE SWITCH“Proof of Closure connections on J18 Pins 2 and 3 are open.”TechnicianSimplicitySimplicity Boiler Manual p. 144
COMM ERR“Occurs if display or main control communications out for 30 seconds.”TechnicianSimplicitySimplicity Boiler Manual p. 141
CONFIG FAULT“Configuration data in the control safety micro does not match that in the control's application micro.”TechnicianSimplicitySimplicity Boiler Manual p. 145
CONFIG MISMATCH“Configuration number stored in the board does not match the configuration number the control reads from the harness.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 64; CGi Series 5 Boiler Manual p. 76; EG Series 7 Boiler Manual p. 74
CONFIRM CONFIGURATION“Board not configured.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 64; CGi Series 5 Boiler Manual p. 76; EG Series 7 Boiler Manual p. 74
CTRL FAULT“Occurs when micro-controllers on main board have a RAM or ROM error.”TechnicianSimplicitySimplicity Boiler Manual p. 141
DAMPER“Damper end switch opened after it had been proven closed.”Technician
5 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3
5 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49
DHW OUT > BLR OUT“DHW Outlet > Boiler Outlet + 10°F and burner has been firing for at least 30 seconds.”TechnicianSimplicitySimplicity Boiler Manual p. 145
DHW OUT SNSR“The DHW Outlet sensor read invalid.”TechnicianSimplicitySimplicity Boiler Manual p. 147
DHW VOLTAGE HIGH“DHW / Thermostat2 input excessive voltage.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 67; CGi Series 5 Boiler Manual p. 79; EG Series 7 Boiler Manual p. 77
DISPLAY COMM“Occurs when display communications out for 30 seconds.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 105; Ultra Series 4 Boiler Manual p. 121
DISPLAY COMM“Occurs if display communications out for 30 seconds”TechnicianECO (no series number on cover), ECO Series 2, WM97+ (no series number on cover), WM97+ Series 2ECO Boiler Manual Series 1 p. 95; ECO Series 2 Boiler Manual p. 100; WM97+ CT Boiler Manual Series 1 p. 107; WM97+ Series 2 Boiler Manual p. 113
EXCEEDED FLOW RATER“*Combi Only* The Combi block has a flow rate above the Maximum Flow Rate for the boiler model.”TechnicianSimplicitySimplicity Boiler Manual p. 148
EXP BOARD COM FAULT“Communication between the Expansion Control Board and the U-Control Board has failed”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
FALSE FLAME“Flame detected when the gas valve is not powered.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 65; CGi Series 5 Boiler Manual p. 77; EG Series 7 Boiler Manual p. 75
FALSE FLAME“Occurs if flame is detected when there should be no flame.”TechnicianEvergreen Series 2, ECO Tec Series 2, ECO Tec (no series number on cover), SimplicityEvergreen Series 2 Boiler Manual p. 160; ECO Tec Series 2 Boiler Manual p. 142; ECO Tec Boiler Manual p. 120; Simplicity Boiler Manual p. 143
FLAME“Flame loss or flame not sensed during trial for ignition.”Technician
7 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
7 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
FLAME CIRCUIT“When the digital flame input does not sense the circuit to have discharged appropriately.”TechnicianSimplicitySimplicity Boiler Manual p. 146
FLAME FAULT“Occurs when flame is detected when there should be no flame.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 105; Ultra Series 4 Boiler Manual p. 121
FLAME FAULT“Occurs if flame is detected when there should be no flame.”Technician
7 seriesECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, WM97+ (no series number on cover), WM97+ Series 2
7 documentsECO Boiler Manual Series 1 p. 96; ECO Series 2 Boiler Manual p. 101; Evergreen Series 1 Boiler p. 113; Evergreen Boiler Manual for Sizes 110-155 p. 110; Evergreen Boiler Manual for Sizes 220-399 p. 108; WM97+ CT Boiler Manual Series 1 p. 108; WM97+ Series 2 Boiler Manual p. 114
FLAME LOSS“Boiler went through 5 ignition attempts and flame value dropped below Proof of Ignition during stabilization time of ignition.”TechnicianSimplicitySimplicity Boiler Manual p. 144
FLAME LOSS FAULT“Flame value dropped below the allowable Proof of Flame threshold while running.”TechnicianEvergreen Series 2Evergreen Series 2 Boiler Manual p. 160
FLAME LOSS FAULT“Boiler went through 5 ignition attempts and ame value dropped below Proof of Ignition during stabilization time of ignition.”TechnicianECO Tec Series 2ECO Tec Series 2 Boiler Manual p. 143
FLAME LOSS FAULT“Boiler went through 5 ignition attempts and flame value dropped below Proof of Ignition during stabilization time of ignition.”TechnicianECO Tec (no series number on cover)ECO Tec Boiler Manual p. 121
FLAME LOST“Flame has been lost during operation.”TechnicianCGa Series 4CGa Series 4 Boiler Manual p. 66
FLAME lights flashing“Flame loss, or flame not sensed during trial for ignition. Boiler may not be properly grounded.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
FLAMER LOST“Flame has been lost during operation.”TechnicianCGi Series 5, EG / PEG Series 7CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
FLUE 1 OPEN“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
FLUE 1 SHORT“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
FLUE 2 OPEN“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
FLUE 2 SHORT“Specified sensor is sensed as Open/Short.”TechnicianSimplicitySimplicity Boiler Manual p. 145
FLUE TEMP TOO HIGH“Occurs if flue temperature sensor exceeds 210°F (Warning) or 220°F (Lockout).”Technician
6 seriesEvergreen Series 2, ECO Tec Series 2, ECO Tec (no series number on cover), Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399
6 documentsEvergreen Series 2 Boiler Manual p. 161; ECO Tec Series 2 Boiler Manual p. 141; ECO Tec Boiler Manual p. 119; Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; Evergreen Boiler Manual for Sizes 220-399 p. 107
FLUE TEMP TOO HIGH“Occurs when flue temperature sensor exceeds 216°F.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 104; Ultra Series 4 Boiler Manual p. 120
FLUE TEMP TOO HIGH“Occurs if flue temperature sensor exceeds 216°F”TechnicianECO (no series number on cover), ECO Series 2, WM97+ (no series number on cover), WM97+ Series 2ECO Boiler Manual Series 1 p. 95; ECO Series 2 Boiler Manual p. 100; WM97+ CT Boiler Manual Series 1 p. 107; WM97+ Series 2 Boiler Manual p. 113
FLUE TOO HIGH“Occurs if flue temperature sensor exceeds 210°F (Warning) or 220°F (Lockout).”TechnicianSimplicitySimplicity Boiler Manual p. 142
Flash code 2*“Internal fault, microprocessor or memory.”Technician
8 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4, GV90+ Series 2
8 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51; GV90+ Series 2 Boiler Manual p. 79
Flash code 3*“Internal fault, LWCO circuit.”TechnicianCGa Series 3, CGi Series 4CGa Series 3 Boiler Manual p. 49; CGi Series 4 Boiler Manual p. 51
Flash code 3*“LWCO circuit.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
Flash code 3*“Unused.”Technician
5 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGi Series 3
5 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGI Series 3 Boiler Manual p. 51
Flash code 4*“Unused.”Technician
8 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4, GV90+ Series 2
8 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51; GV90+ Series 2 Boiler Manual p. 79
Flash code 5*“Internal fault, water thermistors disagree.”Technician
8 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4, GV90+ Series 2
8 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51; GV90+ Series 2 Boiler Manual p. 79
Flash code 6*“Internal fault, gas valve circuit.”TechnicianCGa Series 2, EG & PEG Series 5, EGH Series 4, EG & PEG Series 5, EGH Series 5CGA Series 2 Boiler Manual p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EGH Control Supplement – Universal p. 28
Flash code 6* Flashes once per second“Internal fault, gas valve circuit.”Technician
5 seriesCGa Series 2, EG / PEG Series 6, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
5 documentsCGa Boiler Manual Series 2 p. 49; EG Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
GAS PRESSURE SW FAULT“Gas pressure switch is open (high or low)”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
GAS RELAY 1-4“The control has detected a problem with gas valve output circuit.”TechnicianSimplicitySimplicity Boiler Manual p. 143
GAS RELAY FAULT 1-4“The control has detected a problem with the control board's gas valve output circuit.”TechnicianEvergreen Series 2Evergreen Series 2 Boiler Manual p. 161
GAS RELAY FAULT 1-4“The control has detected a problem with gas valve output circuit.”TechnicianECO Tec Series 2, ECO Tec (no series number on cover)ECO Tec Series 2 Boiler Manual p. 142; ECO Tec Boiler Manual p. 120
GAS VALVE FAULT“The U-Control has detected a problem with it gas valve output circuit”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
GAS VALVE FAULT“The control has detected a problem with gas valve output circuit.”TechnicianEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399Evergreen Series 1 Boiler p. 113; Evergreen Boiler Manual for Sizes 110-155 p. 110; Evergreen Boiler Manual for Sizes 220-399 p. 108
GAS VALVE FAULT“The control module has detected a problem with its gas valve output circuit.”TechnicianECO (no series number on cover), ECO Series 2ECO Boiler Manual Series 1 p. 96; ECO Series 2 Boiler Manual p. 101
GAS VALVE FAULT“The WM97+ control has detected a problem with it gas valve output circuit”TechnicianWM97+ (no series number on cover), WM97+ Series 2WM97+ CT Boiler Manual Series 1 p. 108; WM97+ Series 2 Boiler Manual p. 114
GV FAULT EXPANSION BRD“Gas valve output of the Expansion Board”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
HARDWARE FAULT 1“Control Board Hardware faults – A/D converter fault, flame circuit fault, RAM fault, ROM fault, sequence fault, RAM disagrees fault.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 2“Control Board Internal Relay Error.”TechnicianCGi Series 5CGi Series 5 Boiler Manual p. 78
HARDWARE FAULT 2“Control Board K3 Relay Open Fault.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 3“Control Board K3 Relay Closed Fault.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 4“Control Board K4 Relay Open Fault.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 5“Possible Control board failure or Pilot valve harness short to 24 Vac.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 6“Control Board K5 Relay Open Fault.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 7“Possible Control board failure or Main valve harness short to 24 Vac.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; CGi Series 5 Boiler Manual p. 78; EG Series 7 Boiler Manual p. 76
HARDWARE FAULT 8“Control Board K6 Relay Open Fault.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 66; EG Series 7 Boiler Manual p. 76
HARDWARE FAULTS 3, 4, 6, 8“Control Board Internal Relay Error.”TechnicianCGi Series 5CGi Series 5 Boiler Manual p. 78
HIGH TEMP LIMIT“Boiler temperature sensor reached High Temp Limit setting.”TechnicianEvergreen Series 2, ECO Tec Series 2, ECO Tec (no series number on cover), SimplicityEvergreen Series 2 Boiler Manual p. 161; ECO Tec Series 2 Boiler Manual p. 142; ECO Tec Boiler Manual p. 120; Simplicity Boiler Manual p. 143
HIGH TEMP LIMIT“Boiler temperature sensor reached High Temp Limit setting (no higher than 200°F).”Technician
9 seriesECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, Ultra Series 3 (CT), Ultra Series 4, WM97+ (no series number on cover), WM97+ Series 2
9 documentsECO Boiler Manual Series 1 p. 96; ECO Series 2 Boiler Manual p. 101; Evergreen Series 1 Boiler p. 113; Evergreen Boiler Manual for Sizes 110-155 p. 110; Evergreen Boiler Manual for Sizes 220-399 p. 108; Ultra Series 3-CT Boiler Manual p. 105; Ultra Series 4 Boiler Manual p. 121; WM97+ CT Boiler Manual Series 1 p. 108; WM97+ Series 2 Boiler Manual p. 114
HW FAULT EXPANSION BRD“Expansion Control Board hardware has failed.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 107; Ultra Series 4 Boiler Manual p. 123
IGN FAULT 1“Boiler went through 5 ignition attempts and never detected flame or flame sense value never reached minimum threshold for boiler model.”TechnicianSimplicitySimplicity Boiler Manual p. 144
IGN FAULT 2“Boiler went through 5 ignition attempts and did not meet running flame threshold for boiler model.”TechnicianSimplicitySimplicity Boiler Manual p. 144
IGNITION 1 FAULT“Boiler went through five ignition attempts and either never detected flame, or flame sense value never reached proof of flame threshold of 0.8 uA or greater within the flame proving period.”TechnicianEvergreen Series 2Evergreen Series 2 Boiler Manual p. 162
IGNITION 1 FAULT“Boiler went through five ignition attempts and either never detected flame, or flame sense value never reached proof of flame threshold of 0.8 within 2 seconds.”TechnicianECO Tec Series 3ECO Tec Series 3 Boiler Manual p. 166
IGNITION 1 FAULT“Boiler went through 5 ignition attempts and never detected flame or flame sense value never reached minimum threshold for boiler model.”TechnicianECO Tec Series 2, ECO Tec (no series number on cover)ECO Tec Series 2 Boiler Manual p. 143; ECO Tec Boiler Manual p. 121
IGNITION 2 FAULT“Boiler went through five ignition attempts and did not meet running flame threshold for boiler model within 10 seconds”TechnicianECO Tec Series 3, Evergreen Series 2ECO Tec Series 3 Boiler Manual p. 166; Evergreen Series 2 Boiler Manual p. 162
IGNITION 2 FAULT“Boiler went through 5 ignition attempts and did not meet running flame threshold for boiler model.”TechnicianECO Tec Series 2, ECO Tec (no series number on cover)ECO Tec Series 2 Boiler Manual p. 143; ECO Tec Boiler Manual p. 121
IGNITION FAULT“Maximum number of failed ignitions has been reached.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 65; CGi Series 5 Boiler Manual p. 77; EG Series 7 Boiler Manual p. 75
IGNITION FAULT“Boiler went through 5 ignition attempts and never detected flame.”Technician
6 seriesECO (no series number on cover), ECO Series 2, Ultra Series 3 (CT), Ultra Series 4, WM97+ (no series number on cover), WM97+ Series 2
6 documentsECO Boiler Manual Series 1 p. 97; ECO Series 2 Boiler Manual p. 102; Ultra Series 3-CT Boiler Manual p. 106; Ultra Series 4 Boiler Manual p. 122; WM97+ CT Boiler Manual Series 1 p. 109; WM97+ Series 2 Boiler Manual p. 115
IGNITION FAULT“Boiler went through 5 ignition attempts and never detected flame or flame sense value never reached minimum threshold for boiler model.”TechnicianEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399Evergreen Series 1 Boiler p. 114; Evergreen Boiler Manual for Sizes 110-155 p. 111; Evergreen Boiler Manual for Sizes 220-399 p. 109
INTL DISPL COMM ERR“Occurs when the display loses communication with its radio.”TechnicianSimplicitySimplicity Boiler Manual p. 148
LIMIT“Fault detected in temperature sensing hardware.”Technician
7 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
7 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
LIMIT OPEN“Occurs if manual or automatic reset limit opens.”Technician
11 seriesECO Tec Series 3, Evergreen Series 2, ECO Tec Series 2, ECO Tec (no series number on cover), ECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, WM97+ (no series number on cover), WM97+ Series 2
11 documentsECO Tec Series 3 Boiler Manual p. 166; Evergreen Series 2 Boiler Manual p. 162; ECO Tec Series 2 Boiler Manual p. 142; ECO Tec Boiler Manual p. 120; ECO Boiler Manual Series 1 p. 95; ECO Series 2 Boiler Manual p. 100; Evergreen Series 1 Boiler p. 113; Evergreen Boiler Manual for Sizes 110-155 p. 110; Evergreen Boiler Manual for Sizes 220-399 p. 108; WM97+ CT Boiler Manual Series 1 p. 108; WM97+ Series 2 Boiler Manual p. 114
LIMIT OPEN“Occurs when manual or automatic reset limit opens.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 105; Ultra Series 4 Boiler Manual p. 121
LIMIT light flashing alone“Usually indicates an open or shorted return water temperature sensor.”TechnicianGold GV Series 3, Gold GV Series 4, GV90+ Series 1GV Series 3 Manual p. 70; GV Series 4 Manual p. 70; GV90 Manual p. 77
LIMIT light flashing alone“Usually indicates an open or shorted return water or supply temperature/LWCO sensor.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
LOW FLAME SHUTDOWN“Flame quality dropped below allowable Running Flame Threshold, but it did not go out.”TechnicianECO Tec Series 3, Evergreen Series 2ECO Tec Series 3 Boiler Manual p. 167; Evergreen Series 2 Boiler Manual p. 163
LOW FLAME SHUTDOWN“Occurs if flame quality drops below the desired running value.”TechnicianSimplicitySimplicity Boiler Manual p. 148
LOW WTR CUTOFF OPEN“Occurs when Low Water Cutoff Device contacts open for more than 1 second.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 104; Ultra Series 4 Boiler Manual p. 120
LOW WTR CUTOFF OPEN“Occurs if internal low water cutoff contacts open.”Technician
7 seriesECO Tec Series 2, ECO Tec (no series number on cover), Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, WM97+ (no series number on cover), WM97+ Series 2
7 documentsECO Tec Series 2 Boiler Manual p. 141; ECO Tec Boiler Manual p. 119; Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; Evergreen Boiler Manual for Sizes 220-399 p. 107; WM97+ CT Boiler Manual Series 1 p. 107; WM97+ Series 2 Boiler Manual p. 113
LOW WTR CUTOFF OPEN“Occurs if low water cutoff contacts open.”TechnicianECO (no series number on cover), ECO Series 2ECO Boiler Manual Series 1 p. 95; ECO Series 2 Boiler Manual p. 100
LOW WTR CUTOFF WARNING“Occurs if the LWCO needs to be cleaned.”TechnicianECO Tec Series 3, Evergreen Series 2ECO Tec Series 3 Boiler Manual p. 167; Evergreen Series 2 Boiler Manual p. 163
LWCO“LWCO circuit approaching lockout state. Sensor requires maintenance. LWCO LED will flash 3 times when maintenance is required.”TechnicianEG / PEG Series 6, EGH Series 5, CGa Series 3, CGi Series 4EG Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGi Series 4 Boiler Manual p. 51
LWCO OPEN“Occurs if internal low water cutoff contacts open.”TechnicianSimplicitySimplicity Boiler Manual p. 142
LWCO light flashing alone“Three (3) rapid pulses indicates LWCO requires maintenance.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
MANUAL LIMIT“Manual Limit chain / electrical circuit is open.”TechnicianCGa Series 4, CGi Series 5, EG / PEG Series 7CGa Series 4 Boiler Manual p. 65; CGi Series 5 Boiler Manual p. 77; EG Series 7 Boiler Manual p. 75
OUTDOOR SENSOR“Outdoor temperature sensor short or OPEN.”TechnicianSimplicitySimplicity Boiler Manual p. 148
OUTDOOR SENSOR ERROR“Outdoor temperature sensor short or OPEN.”TechnicianEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399Evergreen Series 1 Boiler p. 114; Evergreen Boiler Manual for Sizes 110-155 p. 111; Evergreen Boiler Manual for Sizes 220-399 p. 109
POWER + DAMPER“Damper stuck closed or unable to close end switch within 45 seconds from TSTAT call.”TechnicianCGa Series 2, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3CGa Boiler Manual Series 2 p. 49; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49
POWER + DAMPER“Damper stuck closed or unable to close end switch within 45 seconds from TSAT call.”TechnicianEG & PEG Series 5, EGH Series 4, EG & PEG Series 5, EGH Series 5EG, PEG, and EGH Control Supplement Manual p. 32; EGH Series 5 Control Supplement – Universal Control Systems p. 28
POWER + FLAME“Flame sensed without call for heat or out of sequence during ignition trial.”Technician
7 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
7 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
POWER + PURGE“Pressure Switch stuck open or closed.”TechnicianCGi Series 3, CGi Series 4CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
POWER + TSTAT/CIRC“High voltage detected on TSTAT circuit.”Technician
7 seriesCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5, CGa Series 3, CGi Series 3, CGi Series 4
7 documentsCGa Boiler Manual Series 2 p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
POWER and DAMPER lights flashing“Usually indicates damper circuit is closed when it should not be, or damper failed to close within 5 minutes.”TechnicianCGa Series 1CGA Series 1 Manual p. 52
POWER and FLAME lights flashing“Usually indicates control has had three unsuccessful ignition attempts or sensed flame when it shouldn't be there.”TechnicianGold GV Series 3GV Series 3 Manual p. 70
POWER and FLAME lights flashing“Flame sensed without a call for heat or out of sequence during ignition trial. Usually indicates control has had three unsuccessful ignition attempts or sensed flame when it shouldn’t be there. Boiler may not be properly grounded.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
POWER and FLAME lights flashing“Usually indicates false flame sense or flame sensed when it shouldn't be there.”Technician
6 seriesCGa Series 1, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2
6 documentsCGA Series 1 Manual p. 52; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47
POWER and FLAME lights flashing“Usually indicates control has had three unsuccessful ignition attempts or sensed flame when it shouldn't be there. Boiler may not be properly grounded.”TechnicianGV90+ Series 1GV90 Manual p. 77
POWER and FLAME lights flashing“Usually indicates false flame sense or flame sensed when it should not be there.”TechnicianCGi 4e Series 2CGI 4e Series 2 Manual p. 49
POWER and FLAME lights flashing“Usually indicates control has had three unsuccessful”TechnicianGold GV Series 4GV Series 4 Manual p. 70
POWER and LIMIT light flashing alternately“Usually indicates that limit circuit failed to cut off boiler at high temperaure — return water temperature sensor has sensed water over 235 °F.”TechnicianGold GV Series 3GV Series 3 Manual p. 70
POWER and LIMIT light flashing alternately“Usually indicates that limit circuit failed to cut off boiler at high temperature — return water temperature sensor has sensed water over 235 °F.”TechnicianGold GV Series 4, GV90+ Series 1GV Series 4 Manual p. 70; GV90 Manual p. 77
POWER and PRES SWITCH lights flashing“Usually indicates pressure switch is closed when it should not be, or pressure switch failed to close within 5 minutes of blower starting.”TechnicianGold GV Series 3GV Series 3 Manual p. 70
POWER and PRESS SWITCH lights flashing“Usually indicates pressure switch is closed when it should not be, or pressure switch failed to close within 5 minutes of blower starting.”TechnicianGV90+ Series 2, Gold GV Series 4, GV90+ Series 1GV90+ Series 2 Boiler Manual p. 79; GV Series 4 Manual p. 70; GV90 Manual p. 77
POWER and PRESS SWITCH lights flashing“Usually indicates pressure switch is closed when it should not be, or pressure switch failed to close within 5 minutes of inducer starting.”Technician
6 seriesCGi 4e Series 2, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2
6 documentsCGI 4e Series 2 Manual p. 49; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47
POWER and TSTAT CIRC lights flashing“Usually indicates stray voltage on external thermostat circuit wires or return water temperature entering boiler sections has not reached 130 °F within 20 minutes.”TechnicianGold GV Series 3GV Series 3 Manual p. 70
POWER and TSTAT CIRC lights flashing“Usually indicates stray voltage on external thermostat circuit wires or return water temperature entering boiler sections has not reached 130°F within 30 minutes.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
POWER and TSTAT CIRC lights flashing“Usually indicates stray voltage on external thermostat circuit wires (usually due to miswired 3-wire zone valve).”Technician
7 seriesCGa Series 1, CGi 4e Series 2, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2
7 documentsCGA Series 1 Manual p. 52; CGI 4e Series 2 Manual p. 49; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47
POWER and TSTAT CIRC lights flashing“Usually indicates stray voltage on external thermostat circuit wires or return water temperature entering boiler sections has not reached 140°F within 20 minutes.”TechnicianGold GV Series 4, GV90+ Series 1GV Series 4 Manual p. 70; GV90 Manual p. 77
POWER light flashing alone“Usually indicates reversed polarity of 120 VAC power wires.”Technician
11 seriesGV90+ Series 2, CGa Series 1, CGi 4e Series 2, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2, Gold GV Series 3, Gold GV Series 4, GV90+ Series 1
11 documentsGV90+ Series 2 Boiler Manual p. 79; CGA Series 1 Manual p. 52; CGI 4e Series 2 Manual p. 49; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47; GV Series 3 Manual p. 70; GV Series 4 Manual p. 70; GV90 Manual p. 77
POWER light on and DAMPER light flashing“Usually indicates the damper circuit opened during the run cycle.”TechnicianCGa Series 1CGA Series 1 Manual p. 52
POWER light on and FLAME light flashing“Usually indicates pilot flame was not established within 15 seconds from application of spark. Control will flash light, but will continue to cycle indefinitely until flame is established or problem is corrected.”Technician
7 seriesCGa Series 1, CGi 4e Series 2, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2
7 documentsCGA Series 1 Manual p. 52; CGI 4e Series 2 Manual p. 49; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47
POWER light on and PRESS SWITCH light flashing“Usually indicates pressure switch opened during the run cycle.”Technician
6 seriesCGi 4e Series 2, CGi Series 2, CGs, CGs 4e, CGt Series 1, CGt Series 2
6 documentsCGI 4e Series 2 Manual p. 49; CGI Series 2 Manual p. 49; CGS Manual p. 45; CGS 4e Manual p. 45; CGt Boiler Manual Series 1 p. 47; CGt Boiler Manual p. 47
POWER; Flashes once per second“120 VAC connection to boiler reversed or there is insufficient earth ground.”Technician
5 seriesCGa Series 2, CGa Series 3, CGi Series 3, CGi Series 4, GV90+ Series 2
5 documentsCGa Boiler Manual Series 2 p. 49; CGa Series 3 Boiler Manual p. 49; CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51; GV90+ Series 2 Boiler Manual p. 79
POWER; Flashes once per second“120 VAC connection to boiler reversed.”TechnicianCGa Series 2, EG & PEG Series 5, EGH Series 4, EG / PEG Series 6, EGH Series 5, EG & PEG Series 5, EGH Series 5CGA Series 2 Boiler Manual p. 49; EG, PEG, and EGH Control Supplement Manual p. 32; EG Control Supplement – Universal p. 28; EGH Control Supplement – Universal p. 28
PREHEAT ACTIVE“Occurs when running the PREHEAT function.”TechnicianSimplicitySimplicity Boiler Manual p. 148
PS OPEN“Air Pressure Switch is open.”TechnicianCGi Series 5CGi Series 5 Boiler Manual p. 79
PURGE“Pressure switch opened after it had been proven closed.”TechnicianCGi Series 3, CGi Series 4CGI Series 3 Boiler Manual p. 51; CGi Series 4 Boiler Manual p. 51
REDUCED TGT - BLR“Boiler Outlet sensor detected above Max Boiler Temp minus Boiler Out On Diff. *Can only occur if using System Supply or DHW Out as a modulation sensor*”TechnicianSimplicitySimplicity Boiler Manual p. 148
REDUCED TGT - FLOW“Boiler Outlet sensor detected > Boiler Inlet sensor + 50°F. Modifies Target temperature to prevent overstressing heat exchanger.”TechnicianSimplicitySimplicity Boiler Manual p. 148
REDUCED TGT - FLUE“Flue temperature detected between 200°F and 210°F. Modifies target temperature to prevent overheating flue.”TechnicianSimplicitySimplicity Boiler Manual p. 148
RETURN > SUPPLY“Occurs when a return water temperature is greater than the corresponding supply temperature by 10°F or more. Applies to system sensors or boiler sensors. Condition must occur for 10 minutes for system sensors.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 104; Ultra Series 4 Boiler Manual p. 120
RETURN > SUPPLY“Occurs if a return water temperature is greater than the corresponding supply temperature by 10°F for more and burner has been lit for more than 60 seconds.”TechnicianECO Tec Series 2ECO Tec Series 2 Boiler Manual p. 141
RETURN > SUPPLY“Occurs if a return water temperature is greater than the corresponding supply temperature by 10º F for more.”TechnicianEvergreen Pro 220/299/300/399Evergreen Boiler Manual for Sizes 220-399 p. 107
RETURN > SUPPLY“Occurs if a return water temperature is greater than the corresponding supply temperature by 10°F or more and burner has been lit for more than 60 seconds.”TechnicianECO Tec (no series number on cover)ECO Tec Boiler Manual p. 119
RETURN > SUPPLY“Occurs if a return water temperature is greater than the corresponding supply temperature by 10°F or more.”Technician
6 seriesECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, WM97+ (no series number on cover), WM97+ Series 2
6 documentsECO Boiler Manual Series 1 p. 94; ECO Series 2 Boiler Manual p. 99; Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; WM97+ CT Boiler Manual Series 1 p. 106; WM97+ Series 2 Boiler Manual p. 112
RETURN SENSOR“Occurs when Return Sensor are chosen as the Target Modulation sensors and the Boiler out sensor is either open or short.”TechnicianSimplicitySimplicity Boiler Manual p. 147
SENSOR GROUND“Three (3) rapid pulses indicates the sensor ground wire may not be connected or the boiler has a poor ground connection or stray voltage on ground.”TechnicianCGa Series 2, CGi Series 3CGa Boiler Manual Series 2 p. 49; CGI Series 3 Boiler Manual p. 51
SOLID LWCO LED“Low water condition occurred.”TechnicianEG / PEG Series 6, EGH Series 5, CGa Series 3, CGi Series 4EG Control Supplement – Universal p. 28; CGa Series 3 Boiler Manual p. 49; CGi Series 4 Boiler Manual p. 51
SOLID SENSOR GROUND LED“and "LCO" on Display”TechnicianCGi Series 3CGI Series 3 Boiler Manual p. 51
SOLID SENSOR GROUND LED and “LCO” on Display“Indicates the sensor ground wire is not grounded or the boiler has a poor ground connection or stray voltage on ground. Check both sensor ground wire on the P5 connection and the boiler ground.”TechnicianCGa Series 2CGa Boiler Manual Series 2 p. 49
SPILL SWITCH“Burner spill caused by possible vent blockage or wind.”TechnicianCGa Series 4, EG / PEG Series 7CGa Series 4 Boiler Manual p. 67; EG Series 7 Boiler Manual p. 77
SUPPLY 58F > RETURN“Boiler Out temperature has exceeded the Boiler In temperature by more than 58°F, when burner is on.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 103; Ultra Series 4 Boiler Manual p. 119
SUPPLY 58F > RETURN“Boiler Out temperature has exceeded the Boiler In temperature by more than 58°F”Technician
7 seriesECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, WM97+ (no series number on cover), WM97+ Series 2
7 documentsECO Boiler Manual Series 1 p. 94; ECO Series 2 Boiler Manual p. 99; Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; Evergreen Boiler Manual for Sizes 220-399 p. 107; WM97+ CT Boiler Manual Series 1 p. 106; WM97+ Series 2 Boiler Manual p. 112
SUPPLY SENSOR“Occurs when Supply Sensor are chosen as the Target Modulation sensors and the Boiler In sensor is either open or short.”TechnicianSimplicitySimplicity Boiler Manual p. 147
SUPPLY WATER TEMPERATURE TOO HIGH“Occurs when the System Supply temperature goes above 200°F when the burner is running.”TechnicianEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; Evergreen Boiler Manual for Sizes 220-399 p. 107
Solid LWCO light“Low water condition occurred.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
Status H“Burner on, running in high fire mode (manually set for test)”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
Status L“Burner on, running in low fire mode (manually set for test)”TechnicianUltra Series 1 & 2, Ultra Series 1 (older manual)Ultra Gas Series 2 Control Supplement p. 17; Ultra Series 1 Boiler Manual p. 38
TANK SENSOR FAULT— BOTTOM“Aqua Logic (CWH) installations only: Occurs if Lower Tank Sensor has electrical shorted (SHORTED) or has become disconnected (OPEN).”TechnicianWM97+ Series 2WM97+ Series 2 Boiler Manual p. 113
TANK SENSOR FAULT— BOTTOM“Aqua Logic (CWH) installations only: Occurs if Lower Tank Sensor has electrical shorted (SHORT) or has become disconnected (OPEN).”TechnicianWM97+ (no series number on cover), WM97+ Series 2WM97+ CT Boiler Manual Series 1 p. 107; WM97+ CT Boiler Manual Series 2 p. 113
TANK SENSOR FAULT—TOP“Aqua Logic (CWH) installations only: Occurs if Upper Tank Sensor has electrical shorted (SHORT) or has become disconnected (OPEN).”TechnicianWM97+ (no series number on cover), WM97+ Series 2WM97+ CT Boiler Manual Series 1 p. 107; WM97+ Series 2 Boiler Manual p. 113
TEMP RISE“Occurs if supply water temperature in heat exchanger rises faster than 20°F over 2 seconds during the first two minutes the burner is on.”TechnicianSimplicitySimplicity Boiler Manual p. 141
TEMP RISE TOO QUICKLY“Occurs if supply water temperature in heat exchanger rises faster than 10°F per second for two seconds during the first two minutes the burner is on.”TechnicianECO Tec Series 3, Evergreen Series 2ECO Tec Series 3 Boiler Manual p. 168; Evergreen Series 2 Boiler Manual p. 164
TEMP RISE TOO QUICKLY“Occurs when supply water temperature in heat exchanger rises faster than 2°F per second during the first two minutes the burner is on.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 103; Ultra Series 4 Boiler Manual p. 119
TEMP RISE TOO QUICKLY“Occurs if supply water temperature in heat exchanger rises faster than 10°F per second during the first two minutes the burner is on.”TechnicianECO Tec Series 2, ECO Tec (no series number on cover)ECO Tec Series 2 Boiler Manual p. 140; ECO Tec Boiler Manual p. 118
TEMP RISE TOO QUICKLY“Occurs if supply water temperature in heat exchanger rises faster than 2°F per second during the first two minutes the burner is on.”Technician
7 seriesECO (no series number on cover), ECO Series 2, Evergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399, WM97+ (no series number on cover), WM97+ Series 2
7 documentsECO Boiler Manual Series 1 p. 94; ECO Series 2 Boiler Manual p. 99; Evergreen Series 1 Boiler p. 111; Evergreen Boiler Manual for Sizes 110-155 p. 108; Evergreen Boiler Manual for Sizes 220-399 p. 106; WM97+ CT Boiler Manual Series 1 p. 106; WM97+ Series 2 Boiler Manual p. 112
TEMPERATURE SENSOR“Occurs when a temperature sensor has electrically shorted (SHORT) or has become disconnected (OPEN).”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 104; Ultra Series 4 Boiler Manual p. 120
TEMPERATURE SENSOR“Occurs when dual temperature sensors values have spread by more that 10°F.”TechnicianUltra Series 3 (CT), Ultra Series 4Ultra Series 3-CT Boiler Manual p. 104; Ultra Series 4 Boiler Manual p. 120
TEMPERATURE SENSOR“Occurs if a temperature sensor has electrically shorted (SHORT) or has become disconnected (OPEN). Occurs if dual temperature sensors values have spread by more that 10°F if the burner is on”TechnicianECO (no series number on cover), ECO Series 2, WM97+ (no series number on cover), WM97+ Series 2ECO Boiler Manual Series 1 p. 95; ECO Series 2 Boiler Manual p. 100; WM97+ CT Boiler Manual Series 1 p. 107; WM97+ Series 2 Boiler Manual p. 113
TEMPERATURE SENSOR FAULT“Occurs if a temperature sensor has electrically shorted (SHORT) or has become disconnected (OPEN). Occurs if dual temperature sensors values have spread by more that 10°F if the burner is on.”TechnicianEvergreen 70/110/155, Evergreen Pro 110/155, Evergreen Pro 220/299/300/399Evergreen Series 1 Boiler p. 112; Evergreen Boiler Manual for Sizes 110-155 p. 109; Evergreen Boiler Manual for Sizes 220-399 p. 107
TSTAT CIRC light flashing alone“Usually indicates return water temperature sensor detects water at boiler return pipe less than 40 °F. Both internal circulators will run continuously, even with no call for heat, until temperature rises.”TechnicianGold GV Series 3, Gold GV Series 4, GV90+ Series 1GV Series 3 Manual p. 70; GV Series 4 Manual p. 70; GV90 Manual p. 77
TSTAT/CIRC light flashing alone (Freeze Protection)“Usually indicates return water temperature sensor detects water at boiler return pipe less than 40°F. Both internal circulators will run continuously, even with no call for heat, until temperature rises.”TechnicianGV90+ Series 2GV90+ Series 2 Boiler Manual p. 79
WRONG J6“Voltage Configuration jumper on J6 installed incorrectly. 24VAC jumper installed when should be 120VAC. 120VAC jumper installed when it should be 24VAC. No jumper installed.”TechnicianSimplicitySimplicity Boiler Manual p. 146
WRONG SOFTWARE“Main control and display software are not compatible.”TechnicianSimplicitySimplicity Boiler Manual p. 148

What to check, code by code

Weil-McLain Ultra Series 1 and 2 error code E02: ignition failed after 5 tries

Checked

Boiler control display or indicator

E02

“Igntion failed after 5 retries”

Technician

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 21; Ultra Series 1 Boiler Manual, p. 41

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E02 is a hard lockout: ignition failed after five attempts. It needs a manual reset; the checks behind it (spark, gas supply, gas valve, venting) are technician work. See what to check

What it means

E02 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers: the control tried to light the burner five times and failed. The quick-reference lists print it “Igntion failed after 5 retries”, with the misspelling as printed (ultra-gas-series-2-control-supplement, p. 21; ultra-series-1-boiler-manual, p. 41). The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28).

The troubleshooting table splits E02 by what happened during the attempts: no spark, a spark but no flame, or a flame with a weak flame signal. Each case has its own list of checks (ultra-gas-series-2-control-supplement, pp. 28–29).

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E02 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, p. 21). The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician. The E02 lists cover the ignition electrode and its cable, the gas supply and gas valve, the vent and air piping, the condensate drain, the burner and heat exchanger, grounding and the control module (ultra-gas-series-2-control-supplement, pp. 28–29).

When to call a licensed technician

All three cases are technician work (ultra-gas-series-2-control-supplement, pp. 28–29):

  • No spark. The ignition electrode cable, its connectors and the ground lead are inspected, and the igniter wire’s resistance is tested.
  • Spark, but no flame. The list starts with the manual gas valve inside the boiler and, on models 80 and 105 only, the plastic line from the gas valve to the air inlet elbow. It goes on to the incoming gas pressure (“If gas pressure is too high, the gas valve regulator will lock up.”), obstructions and air in the gas lines, the vent and air piping (“Restricted vent will not allow boiler to light.”), checks at the gas valve, gas flow at the meter, cleaning the ignition electrode, restrictions in the condensate drain fitting and trap, cleaning the heat exchanger, the venturi gas line and flue gas recirculation. The last step is replacing the gas valve.
  • Flame, but a weak flame signal. The flame is inspected at low and high fire, the electrode and burner are cleaned, and the gas flow is measured at the meter at high fire; if the input is not within about 10% of the boiler rating, the gas valve is replaced. The ground path is checked, and the last step is replacing the control module.

Notes for different models

Weil-McLain words E02 in three places:

Where Wording Source
Hard lockout quick reference, Series 1 and 2 “Igntion failed after 5 retries” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Igntion failed after 5 retries” ultra-series-1-boiler-manual, p. 41
Troubleshooting table, three rows “Ignition failed through 5 attempts:” followed by “NO SPARK OCCURS:”, “Spark occurs, but no flame:” or “Flame occurs, but flame signal strength is low” ultra-gas-series-2-control-supplement, pp. 28–29

The table on page 28 is headed HARD LOCKOUT condition, but its reason column is printed “Reason for soft lockout” (ultra-gas-series-2-control-supplement, p. 28). E03 is tied to E02: if E03 appears after 5 ignition retries, its row says it “indicates same condition as E-02” (ultra-gas-series-2-control-supplement, p. 29).

E02 exists only on the Ultra Series 1 and 2. Other Weil-McLain boilers have their own ignition rows with their own steps. On the Ultra Series 4 the message is IGNITION FAULT, “Boiler went through 5 ignition attempts and never detected flame.” (ultra-series-4-boiler-manual, p. 122). On the AquaBalance Series 2 it is A01, “No burner ignition after five attempts” (aquabalance-series-2-boiler-manual, p. 92). Use the steps for your own series.

Related codes: E03, E00, E07. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E03: ignition or gas valve electrical problem

Checked

Boiler control display or indicator

E03

“Ignition failure or gas valve electrical problem”

Technician

Ultra Series 1 & 2 · Ultra Gas Series 2 Control Supplement, p. 29

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E03 is a hard lockout. The service guide's table calls it an ignition failure or gas valve electrical problem; its quick-reference list says internal control failure. Gas valve and control checks are technician work. See what to check

What it means

E03 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers. The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28).

What E03 stands for depends on which Weil-McLain list you read. The troubleshooting table says “Ignition failure or gas valve electrical problem” (ultra-gas-series-2-control-supplement, p. 29). The quick-reference lists say internal control failure (ultra-gas-series-2-control-supplement, p. 21; ultra-series-1-boiler-manual, p. 41). The steps in the table follow its own wording and split the code by timing:

  • if E03 appears before the boiler tries for ignition, the problem may be the gas valve connection or its harness;
  • if it appears after 5 ignition retries, it “indicates same condition as E-02”, the ignition failure lockout (ultra-gas-series-2-control-supplement, p. 29).

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E03 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, p. 21). The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician. Every step in the E03 row is on the gas valve, its harness, the ignition checks of E02 or the control module (ultra-gas-series-2-control-supplement, p. 29).

When to call a licensed technician

  • E03 before ignition. The row has the technician test the gas valve harness for continuity and the gas valve itself for resistance, between its pins and from each pin to ground (ultra-gas-series-2-control-supplement, p. 29).
  • E03 after five retries. The technician follows the E02 troubleshooting: ignition electrode and cable, gas supply and gas pressure, vent and air piping, condensate drain, burner and gas valve (ultra-gas-series-2-control-supplement, pp. 28–29).
  • The last step of the row is replacing the control module (ultra-gas-series-2-control-supplement, p. 29).

E07, “Gas valve relay error”, is a separate code; its row checks whether the gas valve wiring is shorted to ground and whether the gas valve is defective (ultra-gas-series-2-control-supplement, p. 30).

Notes for different models

For E03, Weil-McLain’s three documents disagree on what the code is:

Where Wording Source
Troubleshooting table, hard lockout codes “Ignition failure or gas valve electrical problem” ultra-gas-series-2-control-supplement, p. 29
Hard lockout quick reference, Series 1 and 2 “Internal control failure (see Troubleshooting)” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Internal control failure” ultra-series-1-boiler-manual, p. 41

The supplement’s own quick-reference entry points to its troubleshooting pages, and the table there is the only place with steps for E03. This page follows the table.

E03 exists only on the Ultra Series 1 and 2. The Ultra Series 4 reports a gas valve circuit problem as the message GAS VALVE FAULT, “The U-Control has detected a problem with it gas valve output circuit” (printed that way), with its own retry and reset rules (ultra-series-4-boiler-manual, p. 123). The Weil-McLain guide shows how to tell the series apart.

Related codes: E02, E07. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E04: power lost after lockout

Checked

Boiler control display or indicator

E04

“Voltage lost after lockout occurred or AC voltage fluctuations on incoming power”

Technician

Ultra Series 1 & 2 · Ultra Gas Series 2 Control Supplement, p. 30

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E04 is a hard lockout: voltage was lost after a lockout, or the incoming power fluctuated. The boiler restarts only after a manual reset; the fixes in the service guide are technician work. See what to check

What it means

E04 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers. The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until it is reset by hand (ultra-gas-series-2-control-supplement, pp. 21, 28).

The troubleshooting table gives E04 two triggers: power was interrupted while another error was present, or the incoming power fluctuated (ultra-gas-series-2-control-supplement, p. 30). The same row names where the fluctuations come from: a power failure, a brown-out, or poor electrical input from a back-up generator. It also says the control module will only restart with a manual reset, even after power loss, so the boiler does not come back on by itself when the power returns.

Check these first

The Ultra Series 2 user’s manual has no code list, so it gives the owner no steps for E04 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. Do not expect the boiler to restart when the power comes back. The control module restarts only with a manual reset (ultra-gas-series-2-control-supplement, p. 30).
  3. The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32). The E04 row’s fixes for poor incoming power are technician work (ultra-gas-series-2-control-supplement, p. 30).

When to call a licensed technician

  • E04 that comes back. For shutdowns caused by poor power, the table’s fix is a Weil-McLain Time Delay Relay, part number 383-500-021, which delays incoming power by 3 minutes so it can stabilize before it reaches the boiler (ultra-gas-series-2-control-supplement, p. 30). Fitting it is technician work on the boiler’s power supply.
  • Severe power fluctuations. The table says the relay may not solve E04 in severe cases, and that an incoming power line filter or an uninterruptible power source (UPS) may correct it (ultra-gas-series-2-control-supplement, p. 30).
  • The fault behind the E04. E04 is set when power is interrupted while another error is present (ultra-gas-series-2-control-supplement, p. 30). The supplement’s note on overrun lockouts says a service technician must troubleshoot the cause and correct it before the boiler goes back into operation (ultra-gas-series-2-control-supplement, p. 9).

Notes for different models

Weil-McLain words E04 in three places, and the wording is not the same:

Where Wording Source
Troubleshooting table, hard lockout codes “Voltage lost after lockout occurred or AC voltage fluctuations on incoming power” ultra-gas-series-2-control-supplement, p. 30
Hard lockout quick reference, Series 1 and 2 “Power lost after lockout (see Troubleshooting)” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Power lost after lockout” ultra-series-1-boiler-manual, p. 41

Only the troubleshooting table mentions fluctuations in the incoming power; the two quick-reference lists name the power loss alone. The steps on this page come from the table.

The supplement’s cover lists the Ultra-80, -105, -155, -230 and -310 of Series 1 and 2, and E04 exists only on these two series. The Ultra Series 3 and 4, ECO Tec, Evergreen, Simplicity, WM97+ and ECO show fault names instead of numbers, and the AquaBalance uses A and F codes, so the E04 row does not apply to them (ultra-series-4-boiler-manual, pp. 118–123; aquabalance-series-2-boiler-manual, p. 92). How to tell the series apart is in the Weil-McLain guide.

Related codes: E05, E06, E11. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E05: internal control or display error

Checked

Boiler control display or indicator

E05

“Internal Control or Display error”

Technician

Ultra Series 1 & 2 · Ultra Gas Series 2 Control Supplement, p. 30

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E05 is a hard lockout worded 'Internal Control or Display error' in the service guide. The guide's fix is replacing the display and its ribbon cable, then the control module, which is technician work. See what to check

What it means

E05 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers that points at the boiler’s electronics: the display or the control module. The troubleshooting table words it “Internal Control or Display error” (ultra-gas-series-2-control-supplement, p. 30). The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28).

The E05 row has two steps, and neither is a reset: replace the display and the display ribbon cable, then replace the control module (ultra-gas-series-2-control-supplement, p. 30). That sets E05 apart from the internal failure codes E06, E08, E09, E15, E16 and E17, whose rows begin “Reset control and retry. If problem persists, replace control module.” (ultra-gas-series-2-control-supplement, p. 30).

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E05 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, p. 21). The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician. Both steps in the E05 row are part replacements (ultra-gas-series-2-control-supplement, p. 30).

When to call a licensed technician

  • Any E05. Replacing the display and its ribbon cable, and then the control module, is technician work inside the boiler’s control (ultra-gas-series-2-control-supplement, p. 30).
  • E05 that returns after the boiler has been restarted. The row has no other step than the two replacements (ultra-gas-series-2-control-supplement, p. 30).

Notes for different models

Weil-McLain words E05 in three places, and the three say different things:

Where Wording Source
Troubleshooting table, hard lockout codes “Internal Control or Display error” ultra-gas-series-2-control-supplement, p. 30
Hard lockout quick reference, Series 1 and 2 “See Troubleshooting” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Internal control failure” ultra-series-1-boiler-manual, p. 41

The Ultra Series 1 manual’s list uses “Internal control failure” for E03, E05, E06, E07, E13 to E17 and E44 alike, while the troubleshooting table gives several of them their own wording, such as “Gas valve relay error” for E07 and “Supply water sensor problem” for E14 (ultra-series-1-boiler-manual, p. 41; ultra-gas-series-2-control-supplement, p. 30). Take the steps from the table.

E05 exists only on the Ultra Series 1 and 2. The Ultra Series 4 has its own display rows, such as DISPLAY COMM, “Occurs when display communications out for 30 seconds.” (ultra-series-4-boiler-manual, p. 121), with its own steps. The Weil-McLain guide shows how to tell the series apart.

Related codes: E06, E11, E44. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E18: outlet water above 210°F

Checked

Boiler control display or indicator

E18

“Outlet water temperature was higher than 210°F”

Technician

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 21; Ultra Series 1 Boiler Manual, p. 41

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E18 is a hard lockout: outlet water went above 210°F. At 203°F the control shows soft lockout b18 instead. It needs a manual reset, and Weil-McLain says a service technician must find and correct the cause. See what to check

What it means

E18 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers: the outlet (supply) water temperature went above 210°F. The troubleshooting table calls it a “Thermal overrun condition” (ultra-gas-series-2-control-supplement, p. 31).

The supplement describes two levels of overrun protection. At 203°F on the supply or the return, the control shows a soft lockout, b18 for the supply or b19 for the return, and does not fire the burner again until the water has dropped 9°F below the target temperature. At 210°F it goes into hard lockout and shows E18 for the supply or E19 for the return (ultra-gas-series-2-control-supplement, p. 9). A soft lockout restarts by itself once the condition is corrected or times out (ultra-gas-series-2-control-supplement, p. 17); E18 does not.

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E18 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel. The supplement’s note right after the E18 description adds that a service technician must troubleshoot the cause and correct it before the boiler goes back into operation (ultra-gas-series-2-control-supplement, p. 9; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician.

When to call a licensed technician

  • Checking the temperature reading. The E18 row has the technician measure the outlet water temperature with a contact thermometer and compare it with the display’s Information mode reading (the “1” in the first digit). If they are not close, a sensor is replaced, and the control module if the new sensor does not solve it (ultra-gas-series-2-control-supplement, p. 31). The row names the “return temperature sensor” at this step, although E18 is the outlet code; that is how it is printed.
  • Water flow through the boiler. Step 1 of the E18 row says this should only happen when the heat demand is lower than the boiler’s lowest firing rate, such as a single small zone, and lists system checks: boiler and system full of water, no trapped air, system piping and components, piping that agrees with the boiler manual, circulator operation, and the outlet sensor’s connector and the sensor itself (ultra-gas-series-2-control-supplement, p. 31). The row for b18, the soft lockout, has the same list with pipe size and circulator capacity added (p. 26). The row for E25, a temperature rise above 58°F, refers to these suggestions as “hard lockout code 18” (p. 31).

Notes for different models

Weil-McLain words E18 in three places:

Where Wording Source
Troubleshooting table, hard lockout codes “Thermal overrun condition – Outlet water temperature above 210 °F.” ultra-gas-series-2-control-supplement, p. 31
Hard lockout quick reference, Series 1 and 2 “Outlet water temperature was higher than 210°F” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Outlet water temperature was higher than 210°F” ultra-series-1-boiler-manual, p. 41

The soft lockout b18 has two wordings as well. The quick-reference lists say the outlet temperature is too high, over 203°F, with the burner off until the outlet water drops 9°F below the target (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38). The troubleshooting table calls it “High limit operation”, with the burner off until the outlet water drops below 203°F minus the ON differential (ultra-gas-series-2-control-supplement, p. 26).

E18 exists only on the Ultra Series 1 and 2. The Ultra Series 4 has a HIGH TEMP LIMIT message with a different number: the boiler temperature sensor reached the High Temp Limit setting, “no higher than 200°F” (ultra-series-4-boiler-manual, p. 121). Use the row for your own series; the Weil-McLain guide shows how to tell them apart.

Related codes: E19, b18, E25. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E28: blower not running

Checked

Boiler control display or indicator

E28

“No signal from blower”

Technician

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 21; Ultra Series 1 Boiler Manual, p. 41

Printed beside the row in the control supplement (p. 21): “Check INFO #6”.

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E28 is a hard lockout for the blower: 'Blower not running' in the troubleshooting table, 'No signal from blower' in the quick-reference lists. No owner steps; a technician checks the blower, wiring and control module. See what to check

What it means

E28 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers: the control does not get the signal it expects from the blower. The troubleshooting table calls it “Blower not running” (ultra-gas-series-2-control-supplement, p. 31), and the quick-reference lists call it “No signal from blower” (ultra-gas-series-2-control-supplement, p. 21; ultra-series-1-boiler-manual, p. 41). The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28).

The display has a blower check of its own. In Information mode, item 6 shows the target outlet water temperature, and if it reads 6._32, the blower has failed (ultra-gas-series-2-control-supplement, p. 20). The quick-reference list prints “Check INFO #6” beside E28 and E29 (ultra-gas-series-2-control-supplement, p. 21).

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E28 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, p. 21). The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician. Every step in the E28 row is a check or a replacement of the blower, its wiring or the control module (ultra-gas-series-2-control-supplement, p. 31).

When to call a licensed technician

All of E28 is technician work. The row’s steps, in order (ultra-gas-series-2-control-supplement, p. 31):

  • The technician reads INFO #6 in Information mode; 6._32 means the blower has failed.
  • The power supply to the blower is checked. If the blower is not getting power, the wiring is inspected, and the control module is replaced if the wiring is correct and in good condition.
  • If the blower is getting power, a further test tells a failed blower from a failed control module, and that part is replaced.

Notes for different models

Weil-McLain words E28 in three places:

Where Wording Source
Troubleshooting table, hard lockout codes “Blower not running” ultra-gas-series-2-control-supplement, p. 31
Hard lockout quick reference, Series 1 and 2 “No signal from blower”, with “Check INFO #6” printed beside the row ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “No signal from blower” ultra-series-1-boiler-manual, p. 41

The Information mode figure sends the reader to “Figure 19, page 28 for hard lockout code 28 or 29”, but the table on page 28 is labelled Figure 18, and the E28 row itself is on page 31 (ultra-gas-series-2-control-supplement, pp. 20, 28, 31).

E29, “Blower signal not zero when it should be”, is the opposite case. Its row says it can happen when the vent faces a windy side of the building and the wind turns the blower as a call for heat starts (ultra-gas-series-2-control-supplement, p. 31).

The Ultra Series 4 does not show E28. Its table has a BLOWER FAULT message, “Blower unable to reach required speed or does not reach 0 RPM when turned off.”, which resets by itself after 1 hour or from the manual reset screen (ultra-series-4-boiler-manual, p. 122). That row and its steps belong to the Series 4. E codes exist only on the Ultra Series 1 and 2; the Weil-McLain guide shows how to tell the series apart.

Related codes: E29, E65, b65. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 error code E37: return sensor open circuit

Checked

Boiler control display or indicator

E37

“Return temperature sensor open circuit”

Technician

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 21; Ultra Series 1 Boiler Manual, p. 41

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, E37 is a hard lockout: the return water temperature sensor reads as an open circuit. It needs a manual reset, and the sensor and wiring checks behind it are technician work. See what to check

What it means

E37 is a hard lockout on Weil-McLain Ultra Series 1 and 2 boilers: the control sees the return water temperature sensor as an open circuit (ultra-gas-series-2-control-supplement, p. 32). An open circuit means no electrical path through the sensor and its wiring, as if it were disconnected. The return sensor reads the water coming back into the boiler; the display’s Information mode shows its reading as item 2 (ultra-gas-series-2-control-supplement, p. 20).

The display flashes the first digit, “E” and the two-digit code, and the boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28). The neighboring codes cover the other sensor faults: E36 is the outlet sensor open circuit, and E32 and E31 are short circuits of the return and outlet sensors (ultra-gas-series-2-control-supplement, p. 32).

Check these first

The Ultra Series 2 user’s manual has no code list and gives the owner no steps for E37 (ultra-gas-series-2-users-manual).

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. The boiler stays off until a manual reset (ultra-gas-series-2-control-supplement, p. 21). The Ultra Series 2 user’s manual says that if the boiler will not operate when there is a call for heat and the piping is not hot, you follow “To turn off gas to the appliance” and call your service technician or gas supplier (ultra-gas-series-2-users-manual, p. 9, step 11). The restart after a hard lockout is described in the control supplement and the Ultra Series 1 Boiler Manual, documents for installers and service technicians: the RESET button on the Ultra display panel (ultra-gas-series-2-control-supplement, pp. 9, 21; ultra-series-1-boiler-manual, p. 32).
  3. Call a qualified service technician. The E37 row deals only with the sensor, the wiring harness and the control module (ultra-gas-series-2-control-supplement, p. 32).

When to call a licensed technician

The whole E37 row is technician work, in this order (ultra-gas-series-2-control-supplement, p. 32):

  • inspecting the return water temperature sensor and its wiring;
  • replacing the sensor if the wiring is correct and in good condition;
  • replacing the low voltage wiring harness if the problem persists;
  • replacing the control module if the new harness does not resolve it.

Notes for different models

Weil-McLain words E37 in three places; only the word “water” differs:

Where Wording Source
Troubleshooting table, hard lockout codes “Return water temperature sensor open circuit.” ultra-gas-series-2-control-supplement, p. 32
Hard lockout quick reference, Series 1 and 2 “Return temperature sensor open circuit” ultra-gas-series-2-control-supplement, p. 21
Hard lockout quick reference, Series 1 “Return temperature sensor open circuit” ultra-series-1-boiler-manual, p. 41

E37 exists only on the Ultra Series 1 and 2, and on them it is a hard lockout. Other series handle a sensor fault differently. On the Ultra Series 4, a shorted or disconnected sensor shows as the message TEMPERATURE SENSOR, which resets by itself when the condition no longer exists (ultra-series-4-boiler-manual, p. 120). On the AquaBalance, F11 is “The CH return water temperature sensor error.”, one of the F codes that reset automatically (aquabalance-series-2-boiler-manual, pp. 92, 95). The Weil-McLain guide shows how to tell the series apart.

Related codes: E36, E32, E31. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 status code 3: burner on for space heating

Checked

Boiler control display or indicator

Status 3

“Burner on for space heating”

Owner can check

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 17; Ultra Series 1 Boiler Manual, p. 38

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, a 3 in the first digit is a status, not a fault: the burner is on for space heating. The digits after it show the outlet water temperature. The service guide calls it normal operation. See what to check

What it means

On the Ultra Series 1 and 2, the display’s first character is the boiler status, and the other digits are the actual (measured) outlet water temperature (ultra-gas-series-2-control-supplement, p. 17). A 3 there means “Burner on for space heating”: the boiler is firing for the heating system, as opposed to 4, which is the burner on for domestic hot water (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38).

The supplement’s troubleshooting chart treats any first digit from 1 to 8 followed by the water temperature as normal operation (ultra-gas-series-2-control-supplement, p. 24). The full list of status digits, in Weil-McLain’s order (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38):

First digit Status
0 Standby, no call for heat
1 Pre-purge (10 seconds) or post-purge (15 seconds)
2 Ignition
3 Burner on for space heating
4 Burner on for DHW (domestic hot water) heating
5 Checking airflow before prepurge
6 Burner off because the temperature setting has been reached
7 Pump on after a space heating cycle, for a 10-second run-on
8 Pump on after a DHW heating cycle, for a 30-second run-on
H, L Burner on in high or low fire mode, manually set for a test

Check these first

A 3 needs no action. What you can read from the display:

  1. The digits after the 3 are the outlet water temperature (ultra-gas-series-2-control-supplement, p. 17).
  2. After a space heating cycle the first digit can show 7: the pump stays on for a run-on of 10 seconds (ultra-gas-series-2-control-supplement, p. 17).
  3. A lockout looks different. A soft lockout alternates 9 and b with a two-digit code and clears by itself when the condition is corrected or times out (ultra-gas-series-2-control-supplement, p. 17). A hard lockout flashes E with a two-digit code and needs a manual reset (ultra-gas-series-2-control-supplement, p. 21). Look those codes up in the Weil-McLain code table.

When to call a licensed technician

  • Not for a 3 on its own: the supplement’s chart calls it normal operation (ultra-gas-series-2-control-supplement, p. 24).
  • When the display shows a hard lockout (E and a code). Each E code’s row in the supplement lists technician checks and part replacements (ultra-gas-series-2-control-supplement, pp. 28–32).
  • If you smell gas, follow the steps at the top of this page first.

Notes for different models

Unlike the Ultra E codes, which Weil-McLain words differently in its quick-reference lists and its troubleshooting tables, the status digits have the same wording in both places where they are printed: the control supplement and the Ultra Series 1 Boiler Manual (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38).

The status digit exists only on the Ultra Series 1 and 2; the manuals of the other series have no numbered status digit. The Ultra Series 3 and 4, ECO Tec, Evergreen, Simplicity, WM97+ and ECO show text messages, and the cast-iron boilers use indicator lights. The AquaBalance has its own D codes for normal states, D1 to D3 (aquabalance-series-2-boiler-manual, p. 68). The Weil-McLain guide shows how to tell the series apart.

Related codes: Status 4, Status 0, Status 7. All Weil-McLain codes

Weil-McLain Ultra Series 1 and 2 status code 6: burner off, temperature reached

Checked

Boiler control display or indicator

Status 6

“Burner off because temperature setting has been reached”

Owner can check

Ultra Series 1 & 2, Ultra Series 1 (older manual) · Ultra Gas Series 2 Control Supplement, p. 17; Ultra Series 1 Boiler Manual, p. 38

Short answer On Weil-McLain Ultra Series 1 and 2 boilers, a 6 in the first digit means the burner is off because the temperature setting has been reached. It is a status, not a lockout. If the boiler does not restart on its own, call a technician. See what to check

What it means

On the Ultra Series 1 and 2, the first character of the display is the boiler status and the other digits are the measured outlet water temperature (ultra-gas-series-2-control-supplement, p. 17). A 6 in the first position means “Burner off because temperature setting has been reached” in both of Weil-McLain’s status lists (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38).

It is one of the normal operating states. The supplement’s troubleshooting chart says that a first digit from 1 to 8 followed by the water temperature “is normal operation” (ultra-gas-series-2-control-supplement, p. 24). A lockout looks different: a soft lockout alternates 9 with b and a two-digit code, and a hard lockout flashes E with a two-digit code (ultra-gas-series-2-control-supplement, pp. 17, 21).

Check these first

  1. Read the rest of the display. The digits after the 6 are the outlet water temperature (ultra-gas-series-2-control-supplement, p. 17).
  2. Give the boiler time to cool. The supplement’s chart for a boiler that is not firing with a 6 in the first digit says the water may have passed the limit setting, and that the boiler will restart after the water temperature has dropped below that setting minus the differential (ultra-gas-series-2-control-supplement, p. 24).
  3. If the display changes to 9 and b, or starts flashing E, the boiler has gone into a soft or hard lockout; look that code up in the Weil-McLain code table (ultra-gas-series-2-control-supplement, pp. 17, 21).
  4. If the boiler stays on 6 and does not restart, call a qualified service technician. The same chart’s second possibility, a lost flame signal, is also expected to end in a restart; when it does not, the steps that follow are technician work (ultra-gas-series-2-control-supplement, p. 24).

When to call a licensed technician

The chart gives the technician two paths (ultra-gas-series-2-control-supplement, p. 24):

  • Water above the limit setting (parameter 4). The boiler shut down on limit, and the chart sends the technician to the corrective actions for soft lockout code 18: boiler and system full of water, trapped air, piping, circulator operation and the outlet sensor (ultra-gas-series-2-control-supplement, p. 26).
  • Water not above the limit. The control may have lost the flame signal. The technician checks the flame signal, checks gas flow, incoming gas pressure, gas line size and the gas regulator, inspects and cleans the ignition electrode and its wiring, and if the problem persists services the burner with the boiler’s maintenance kit.

Notes for different models

Unlike the Ultra E codes, which Weil-McLain words differently in its quick-reference lists and its troubleshooting tables, the status digit has the same wording in both places where it is printed: the control supplement and the Ultra Series 1 Boiler Manual (ultra-gas-series-2-control-supplement, p. 17; ultra-series-1-boiler-manual, p. 38).

The status digit exists only on the Ultra Series 1 and 2. On the AquaBalance, a similar state has its own code: D2 is displayed when the required boiler water set-point is reached (aquabalance-series-2-boiler-manual, p. 68). The other series show text messages or indicator lights, and none of their tables has a numbered status digit. The Weil-McLain guide shows how to tell the series apart.

Related codes: Status 3, Status 0, b18. All Weil-McLain codes

Weil-McLain AquaBalance error code A01: no burner ignition

Checked

Boiler control display or indicator

A01

“No burner ignition after five attempts”

Technician

AquaBalance Series 2 · AquaBalance Series 2 Boiler Manual, p. 92

Short answer On Weil-McLain AquaBalance Series 2 boilers, A01 means no burner ignition after five attempts; the Series 1 manual calls it 'Lockout indication'. The user's manuals give the owner no reset and no steps for A01. Call a technician. See what to check

What it means

A01 is an “A” code on the Weil-McLain AquaBalance: a lockout that stops the boiler until it is reset by hand (aquabalance-series-2-boiler-manual, p. 92). The Series 2 boiler manual words it “No burner ignition after five attempts” (aquabalance-series-2-boiler-manual, p. 92). The Series 1 manual’s code list says only “Lockout indication”, and its cause table names the fault “No burner ignition” (aquabalance-boiler-manual, pp. 88–89). When a fault occurs, the display flashes together with the fault symbol and shows the code (aquabalance-series-2-boiler-manual, p. 92).

The AquaBalance also has a status code for failed ignition tries. D3 means the boiler has made 3 tries for ignition and failed, and a re-trial delay is in effect for 3 more tries (aquabalance-series-2-boiler-manual, p. 68). The boiler manual’s numbers do not agree with each other: its ignition-safety test says the boiler tried to ignite three times (d3) before the A01 lockout (p. 83), and its sequence of operation says the boiler goes into lockout A01 after 5 attempts (p. 90).

Check these first

The AquaBalance user’s manuals give no reset procedure and no steps for A01. The one owner item below, the condensate drain check, comes from the user’s manuals.

  1. If you smell gas, stop and follow the steps at the top of this page.
  2. Look at the condensate drain. The user’s manual has the owner inspect the condensate drain tubing and the end of the tube, inspect the trap under the boiler, check it for sediment and clean it out if necessary, make sure it has water in it, and contact a boiler service technician about any problem. A trap with no water inside means contacting a boiler service technician immediately (aquabalance-series-2-user-manual, p. 8; the Series 1 manual says the same, aquabalance-series-1-user-manual, p. 8). A blocked condensate trap, or a drain hose looped so that it makes a second trap, is one of the A01 causes in the boiler manual (aquabalance-series-2-boiler-manual, p. 93).
  3. The reset is described only in the boiler manual, which is for use only by the qualified installer or service technician (aquabalance-series-2-boiler-manual, p. 2), and in the Quick Start Guide. The user’s manuals only name the “Reset / OTC button” (aquabalance-series-2-user-manual, p. 11). The boiler manual says an A code is cleared with the RESET button on the front panel (1 second), at most 5 resets in 24 hours, and “Do not leave the boiler operating without a complete diagnosis.” (aquabalance-series-2-boiler-manual, p. 92). The Quick Start Guide gives 1.5 seconds (aquabalance-control-module-quick-start-guide, p. 13).
  4. If A01 comes back, call a qualified service technician.

When to call a licensed technician

On a new installation, the Quick Start Guide says to have the contractor verify that the gas supply is purged (aquabalance-control-module-quick-start-guide, p. 13).

The A01 cause table in the boiler manual lists these checks, all of them technician work (aquabalance-series-2-boiler-manual, p. 93):

  • No gas: check the gas flow to the boiler and that the air has been eliminated from the pipes.
  • The ignition/detection electrode: its wiring, position and deposits, and whether it is deformed or misaligned or has the wrong gap (5/32”).
  • Combustion: a combustion test for natural gas or LP per the manual’s charts.
  • The gas valve, replaced if necessary, and the gas supply pressure.
  • The condensate trap, checked and cleaned. The same row adds: “Also inspect gas valve, blower, venturi, igniter, and heat exchanger, and replace those with signs of damage.”

The Quick Start Guide adds a dirty heat exchanger overdue for cleaning and maintenance to the list, and gives the gas supply pressure spec as “3.5 to 11 w.c.” (aquabalance-control-module-quick-start-guide, p. 13). Its ignitor gap check starts by shutting off the gas supply and removing the ignitor; that is service work, not an owner task (aquabalance-control-module-quick-start-guide, p. 15).

Notes for different models

Document A01 wording Reset Source
AquaBalance Series 2 Boiler Manual (September 2024) “No burner ignition after five attempts” RESET button, 1 second aquabalance-series-2-boiler-manual, p. 92
AquaBalance Boiler Manual, Series 1 (January 2018) “Lockout indication”; cause table: “No burner ignition” RESET button, 1 second aquabalance-boiler-manual, pp. 88–89
Control Module Quick Start Guide (Series 1 and 2) “No burner ignition” reset button, 1.5 seconds aquabalance-control-module-quick-start-guide, p. 13

The 3.5 to 11 w.c. figure is in the Quick Start Guide only, not in the boiler manual’s A01 row.

A01 is an AquaBalance code. The Ultra Series 1 and 2 report their ignition lockout as E02, “Igntion failed after 5 retries”, and the Ultra Series 4 as IGNITION FAULT, each with its own steps (ultra-gas-series-2-control-supplement, p. 21; ultra-series-4-boiler-manual, p. 122). On the AquaBalance, codes such as b01 to b28 are setup parameters, not faults, and have nothing to do with the Ultra’s b codes (aquabalance-series-2-boiler-manual, p. 98).

Related codes: A06, A02, D3. All Weil-McLain codes

How to reset a Weil-McLain boiler

The reset depends on the control, and Weil-McLain’s manuals describe a different one for nearly every series. Find your series below (the table under Find your series helps) and use only the procedure in your series’ user’s manual. The user’s manuals of the Ultra Series 1 and 2, the AquaBalance and the GV90+ Series 2 give the owner no reset; the second list below shows what the installer’s and technician’s documents describe, as information and not as steps for the owner. A reset restarts the boiler; it does not remove the cause. The ECO Tec user’s manuals end their reset steps with “Call for service if fault continues.” (eco-tec-series-3-user-manual, p. 11).

Screen controls, as the user’s manuals describe them:

  • ECO Tec Series 1, 2 and 3: during a fault the status changes to LOCKOUT. “The user will have to select reset on the screen”, then press the Reset button on the screen that follows (eco-tec-series-3-user-manual, p. 11; eco-tec-series-2-users-manual, p. 11; eco-tec-series-1-users-manual, p. 11).
  • Evergreen Series 2: the same steps, and the lockout screen figure says to “highlight and select MANUAL RESET to reset boiler” (evergreen-series-2-user-manual, p. 12).
  • Evergreen Pro 110/155 and 220–399 (user’s manuals of December 2020): the status changes to LOCKOUT, the Time & Date line alternates with the fault name, and a MANUAL RESET line appears on the Boiler Status screen. “Select MANUAL RESET to reset fault condition.” (evergreen-users-manual-for-sizes-110-155, p. 11; evergreen-users-manual-for-sizes-220-399, p. 11)
  • Simplicity: the RESET button takes you to a reset screen with all active errors, and “the user will have to press and hold the RESET button on the final screen shown” (simplicity-users-manual, p. 11).
  • Ultra Series 3 and Series 4: the U-Control display turns red when the boiler locks out; “select MANUAL RESET to reset boiler” (ultra-gas-series-3-users-manual, p. 10; ultra-series-4-user-manual, p. 10).
  • CGa Series 3, CGi Series 4 and EG Series 6 (one shared user’s manual) and EG Series 7: the control shuts the boiler down if the air or vent is blocked. The manuals have you remove blockages that are easily accessible and removable, and then: “If the boiler indicates a manual reset lockout, select <Reset Lockout> on the control display”. A blockage you cannot remove is for a qualified service technician (cga-series-3-users-manual, p. 4; eg-series-7-user-manual, p. 4). For the pressure switch, which the EG Series 7 manual lists for LGB Series 3 and CGi only, the reset is to “press Enter (square symbol), and use the arrow keys to select YES” (eg-series-7-user-manual, p. 12).
  • WM97+ and ECO: the lockout screen turns red, and the figure caption in both user’s manuals says to “highlight and select MANUAL RESET to reset boiler” (wm97-ct-user-manual, p. 11; eco-users-manual, p. 11). The ECO manual lists the steps: the status changes to LOCKOUT, “Select MANUAL RESET to reset fault condition.”, and “Call for service if fault continues.” (eco-users-manual, p. 11).

Series whose user’s manual gives the owner no reset (from documents for installers and service technicians, not steps for the owner):

  • Ultra Series 1 and 2: the Ultra Series 2 user’s manual has no code list and no reset procedure (ultra-gas-series-2-users-manual). The control supplement and service guide says it “must only be used by a qualified heating installer/service technician” (ultra-gas-series-2-control-supplement, p. 1). It says a hard lockout, shown as a flashing E code, “requires manual RESET” (p. 21), that the restart is “manually pressing the Ultra display panel reset button” (p. 9), and that RESET also restarts the boiler from a soft lockout “without waiting for timeouts” (p. 17). Its note on page 9 adds that a service technician must troubleshoot the cause and correct it before the boiler goes back into operation.
  • AquaBalance Series 1 and 2: the user’s manuals give no reset procedure; they only name the “Reset / OTC button” in the control legend (aquabalance-series-2-user-manual, p. 11). The boiler manual, “for use only by your qualified heating installer/service technician” (aquabalance-series-2-boiler-manual, p. 2), says A codes are lockouts that “can only be cleared by the reset key at the boiler front panel”, with the RESET button held for 1 second or RESET on the optional remote timer control if one is installed (p. 92; aquabalance-boiler-manual, p. 88). It limits resets to 5 in 24 hours and says: “Make sure to determine the causes of outages. Do not leave the boiler operating without a complete diagnosis.” F codes clear by themselves once the value is back in the normal range (p. 92). The separate Control Module Quick Start Guide says to push the reset button for 1.5 seconds (aquabalance-control-module-quick-start-guide, pp. 7, 13).
  • GV90+ Series 2: the user’s manual has no reset procedure. The boiler manual says: “To reset control after a lockout, turn off power at the 120V AC service switch or turn down all thermostats. Wait 45 seconds. Then restore power and call for heat.” (gv90-series-2-boiler-manual, p. 79)

Boilers with indicator lights:

  • Older boilers with a pilot lit by match (CGi Series 2, CGs, and EG, PEG and EGH Series 4): the reset button in their user’s manuals is part of the pilot lighting procedure. If the reset button stays depressed after release, the manuals say to stop and immediately call your service technician or gas supplier (cgi-series-2-users-manual, p. 13; cgs-users-manual, p. 13; eg-peg-and-egh-series-4-users-manual, p. 13).

If the fault comes back after a reset, the user’s manuals send you to service: “Call for service if fault continues.” (eco-tec-series-3-user-manual, p. 11) and “If fault re-occurs, contact a service technician.” (eg-series-7-user-manual, p. 12).

These pages cover Weil-McLain gas boilers. Oil-fired boilers such as the Ultra Oil, WGO, WTGO and SGO are not included.

How to read a Weil-McLain code

Letter-and-number codes such as E04 or A01 exist only on the Ultra Series 1 and 2 and on the AquaBalance. The other series with a display show the fault by name, and the cast-iron boilers use indicator lights. The same number or name can mean different things on different controls, so read the row for your series.

Ultra Series 1 and 2: status digit, b codes and E codes

After the display shows “Stby” briefly, the first character is the boiler status and the other digits are the outlet water temperature (ultra-gas-series-2-control-supplement, p. 17). The status digits run from 0, standby with no call for heat, to 8, plus H and L for test modes; status 3 has the full list. A 6 in that position means the burner is off because the temperature setting has been reached (ultra-gas-series-2-control-supplement, p. 17).

  • Soft lockout: the display alternates between 9 with the water temperature and b with a two-digit code, such as b18. The boiler starts again by itself when the condition is corrected or times out (ultra-gas-series-2-control-supplement, p. 17).
  • Hard lockout: the display flashes the first digit, “E” and the two-digit code, as in E04 or E02. It needs a manual reset (ultra-gas-series-2-control-supplement, pp. 21, 28).

The same number can be both. b18 is the soft lockout at a supply (outlet) water temperature of 203°F and E18 the hard lockout at 210°F (ultra-gas-series-2-control-supplement, p. 9). Weil-McLain also words the E codes differently in three places: the quick-reference list in the supplement, the one in the Ultra Series 1 Boiler Manual, and the supplement’s troubleshooting tables. E03, for example, is “Internal control failure” in both lists and “Ignition failure or gas valve electrical problem” in the table (ultra-gas-series-2-control-supplement, pp. 21, 29; ultra-series-1-boiler-manual, p. 41). The E code pages on this site show all three wordings.

The Ultra lists have no code 63 or 66 (ultra-gas-series-2-control-supplement, pp. 17, 21, 26–32). On the AquaBalance, A63 is “E2 prom error” and F66 is “Software doesn’t match.” (aquabalance-series-2-boiler-manual, pp. 92, 95).

AquaBalance: A, F and D codes

When the AquaBalance has a fault, the display flashes together with the fault symbol and shows the code (aquabalance-series-2-boiler-manual, p. 92).

  • A codes, such as A01, are lockouts that need the manual reset (aquabalance-series-2-boiler-manual, p. 92).
  • F codes cause temporary shutdowns that reset automatically when the value returns to the normal range. The Series 2 manual calls them “Automatic Reset type lock-out codes”, the Series 1 manual “Blocking condition codes” (aquabalance-series-2-boiler-manual, p. 92; aquabalance-boiler-manual, p. 88).
  • D1, D2 and D3 are part of normal control operation and typically appear during start-up (aquabalance-series-2-boiler-manual, p. 68). D2, for example, is displayed when the required boiler water set-point is reached.
  • b01 to b28 are setup parameters, not fault codes (aquabalance-series-2-boiler-manual, p. 98). They have nothing to do with the Ultra’s b codes.

Screen controls: the message is the code

The ECO Tec, Evergreen, Simplicity, Ultra Series 3 and 4, WM97+, ECO, CGa Series 4, CGi Series 5 and EG Series 7 show the fault by name. Examples: IGNITION FAULT and LIMIT OPEN on the Ultra Series 4 (ultra-series-4-boiler-manual, pp. 121–122), IGNITION 1 FAULT on the ECO Tec Series 3 (eco-tec-series-3-boiler-manual, p. 166), and the shorter IGN FAULT 1 and LWCO OPEN on the Simplicity (simplicity-boiler-manual, pp. 142, 144).

The screen in lockout looks different by series:

  • ECO Tec Series 3: the display toggles, with a red banner. A constant red screen marks conditions after which the boiler restarts by itself if the condition self-corrects (eco-tec-series-3-boiler-manual, p. 161).
  • Ultra Series 4 and WM97+ Series 2: the display toggles, with the screen flashing red to gray (ultra-series-4-boiler-manual, p. 117; wm97-series-2-boiler-manual, p. 110).
  • ECO Series 2: flashing red for a manual reset lockout, solid red for an automatic reset lockout, and in both the boiler accepts no calls for heat. Solid red on standby only is a warning; the boiler runs but may not run as efficiently (eco-series-2-boiler-manual, p. 97).

A message name does not carry its numbers from one series to another. TEMP RISE TOO QUICKLY means a rise faster than 2°F per second on the Ultra Series 4, and faster than 10°F per second for two seconds on the ECO Tec Series 3 (ultra-series-4-boiler-manual, p. 119; eco-tec-series-3-boiler-manual, p. 168). FLUE TEMP TOO HIGH is 216°F on the Ultra Series 4, and 210°F for a warning or 220°F for a lockout on the ECO Tec Series 2 (ultra-series-4-boiler-manual, p. 120; eco-tec-series-2-boiler-manual, p. 141).

Cast-iron boilers: indicator lights

The GV90+, CGa Series 1 to 3, CGi Series 2 to 4, CGs, CGt, older EG, PEG and EGH, and Gold GV boilers use indicator lights (POWER, TSTAT/CIRC, FLAME, LIMIT and others) and flash codes such as “Flash code 2*”. The tables group them into hard lockout, soft lockout and caution summaries (cga-series-3-boiler-manual, p. 49).

All lights flashing on the CGa Series 3 means “Failure to establish pilot flame after 4 attempts.” (cga-series-3-boiler-manual, p. 49). The CGa Series 2 manuals mark the same row “Propane Gas Only” in the 2012 edition and say that propane requires a manual reset in the 2019 edition, both pointing to pages 34 and 35 of their manual (cga-series-2-boiler-manual, p. 49; cga-boiler-manual-series-2, p. 49).

The same light can mean different things. Flash code 3* is “Unused.” on the CGi Series 3, “Internal fault, LWCO circuit.” on the CGa Series 3 and CGi Series 4, and “LWCO circuit.” on the GV90+ Series 2 (cgi-series-3-boiler-manual, p. 51; cga-series-3-boiler-manual, p. 49; cgi-series-4-boiler-manual, p. 51; gv90-series-2-boiler-manual, p. 79).

Find your series

The series decides which table and which reset apply. For the Ultra Series 1 and 2, read the boiler rating plate to find the series number. The Ultra Series 2 user’s manual says the plate “is located on the right side of the boiler” (ultra-gas-series-2-users-manual, p. 1); the control supplement says it is “located inside the boiler jacket, on the right rear interior panel” (ultra-gas-series-2-control-supplement, p. 1). When you call about an ECO Tec, the user’s manual asks for the boiler model number from the boiler rating label and the Consumer Protection (CP) number from the boiler cabinet (eco-tec-series-3-user-manual, p. 2).

Series (sizes on the manual cover) What the display shows Code table Manual posted on weil-mclain.com under
Ultra Series 1 and 2 (Ultra-80, -105, -155, -230, -310) Status digit, b codes, E codes ultra-gas-series-2-control-supplement, pp. 17, 21, 26–32; ultra-series-1-boiler-manual, pp. 38, 41 Discontinued Products
Ultra Series 3 Messages ultra-series-3-ct-boiler-manual-b, pp. 102–107 Discontinued Products
Ultra Series 4 Messages ultra-series-4-boiler-manual, pp. 118–123 current product page
ECO Tec Series 2 and 3 (80, 110, 150, 199) Messages eco-tec-series-3-boiler-manual, pp. 163–168; eco-tec-series-2-boiler-manual, pp. 140–147 current product page
ECO Tec, first edition (no series number on the cover) Messages eco-tec-series-1-boiler-manual, pp. 118–125 Discontinued Products
Evergreen Series 2 (110 to 399) Messages evergreen-series-2-boiler-manual, pp. 157–164 current product page
Evergreen Pro 110/155 and 220/299/300/399 Messages evergreen-boiler-manual-for-sizes-110-155, pp. 108–111; evergreen-boiler-manual-for-sizes-220-399, pp. 106–109 current product page
Evergreen 70/110/155 Messages evergreen-series-1-boiler-manual, pp. 111–114 Discontinued Products
Simplicity (110, 150, 199) Short messages simplicity-boiler-manual, pp. 141–148 current product page
WM97+ and ECO (70, 110, 155) Messages wm97-series-2-boiler-manual, pp. 112–115; eco-series-2-boiler-manual, pp. 99–102 Discontinued Products
AquaBalance Series 2 (80, 120, 155) A, F and D codes aquabalance-series-2-boiler-manual, pp. 92, 95 current product page
AquaBalance (Series 1) A, F and D codes aquabalance-boiler-manual, pp. 88, 91 Discontinued Products
CGa Series 4, CGi Series 5, EG and PEG Series 7 Messages cga-series-4-boiler-manual, pp. 64–67; cgi-series-5-boiler-manual, pp. 76–79; eg-series-7-boiler-manual-b, pp. 74–77 Resource Library
GV90+ Series 2 Indicator lights gv90-series-2-boiler-manual, p. 79 current product page
CGa Series 1 to 3, CGi Series 2 to 4, CGs, CGt, older EG, PEG and EGH, Gold GV, GV90+ Series 1 Indicator lights for example cga-series-3-boiler-manual, p. 49; cgi-series-4-boiler-manual, p. 51 Discontinued Products or Resource Library

The last column is where weil-mclain.com posted the manual on October 23, 2026, not a statement by Weil-McLain about the product. The documents carry only a part number with a month and year, so they do not say which edition goes with which boiler. For some series two editions are posted, for example the Ultra Series 4 (July 2023 and October 2025) and the AquaBalance Series 2 (July 2018 and September 2024); the code table on this site uses the newer one.

The pressure gauge and the condensate drain

Two of the owner’s maintenance checks matter here: the pressure/temperature gauge and the condensate drain. In the ECO Tec Series 3 user’s manual’s schedule, the gauge is a daily check and the condensate drain a monthly one (eco-tec-series-3-user-manual, p. 5). What to look for depends on the series.

The gauge check is that the reading does not exceed a set number, and if the problem persists, you contact a qualified service technician (eco-tec-series-2-users-manual, p. 6; ultra-gas-series-3-users-manual, p. 6). On the ECO Tec, Evergreen and Ultra Series 2 manuals, higher pressure “may indicate a problem with the expansion tank” (eco-tec-series-2-users-manual, p. 6). The number:

  • 24 psig on the ECO Tec Series 1, 2 and 3, AquaBalance, Simplicity, WM97+, ECO, Evergreen Pro 110/155, Ultra Series 2 and GV90+ Series 2 (eco-tec-series-3-user-manual, p. 6; eco-tec-series-2-users-manual, p. 6; eco-tec-series-1-users-manual, p. 6; aquabalance-series-2-user-manual, p. 7; aquabalance-series-1-user-manual, p. 7; simplicity-users-manual, p. 6; wm97-ct-user-manual, p. 6; eco-users-manual, p. 6; evergreen-users-manual-for-sizes-110-155, p. 6; ultra-gas-series-2-users-manual, p. 6; gv90-series-2-user-manual, p. 6).
  • 24 psig “if using a 30 psig relief valve (typical installation)” on the Evergreen Series 2 and Evergreen Pro 220–399 (evergreen-series-2-user-manual, p. 6; evergreen-users-manual-for-sizes-220-399, p. 6).
  • 25 psig on the Ultra Series 3 and 4 (ultra-gas-series-3-users-manual, p. 6; ultra-series-4-user-manual, p. 6).

The GV90+ Series 2 and Gold GV Series 3 user’s manuals add a minimum before you start the boiler: if the boiler and system are full of water and properly pressurized, “the gauge should read at least 12 psig on most systems” (gv90-series-2-user-manual, p. 12; gv-series-3-users-manual, p. 12). None of the user’s manuals gives the owner a normal operating range or a procedure for adding water or lowering the pressure.

The condensate drain check differs more:

  • ECO Tec Series 1 and 2, Evergreen Pro 110/155, WM97+ and ECO: inspect the drain tubing and its end and make sure condensate can run freely; check that the ball float in the trap under the boiler is in place and free to move and that the trap has water in it; contact a boiler service technician if you see any problem (eco-tec-series-2-users-manual, p. 7; evergreen-users-manual-for-sizes-110-155, p. 7; wm97-ct-user-manual, p. 7; eco-users-manual, p. 7).
  • AquaBalance Series 1 and 2: inspect the drain tubing and its end; inspect the condensate trap under the boiler, check it for sediment and clean it out if necessary, and make sure it has water; contact a boiler service technician about any problem. Both manuals add that a trap with no water inside means contacting a boiler service technician immediately (aquabalance-series-1-user-manual, p. 8; aquabalance-series-2-user-manual, p. 8).
  • Ultra Series 2, 3 and 4 and Evergreen Series 2: the vent may not produce enough condensate to keep the trap full, and a trap that is not full can let small amounts of flue products into the boiler room through the drain line or tee. With the boiler running, hold your fingers in front of the end of the drain tubing and the open top of the tee; escaping flue gas means a dry trap, and a technician should inspect the boiler and drain line if that keeps happening (ultra-gas-series-2-users-manual, p. 7; ultra-gas-series-3-users-manual, p. 7; ultra-series-4-user-manual, p. 7; evergreen-series-2-user-manual, p. 7). To check the line, pour water slowly into the top of the PVC tee on the side of the boiler; it should run out of the end of the drain line, and if it does not, a technician cleans or replaces the line (evergreen-series-2-user-manual, p. 7; ultra-series-4-user-manual, p. 7). To fill a dry trap, temporarily plug the end of the drain line, pour water slowly into the 1/2-inch plastic tee until it fills the drain line and overflows into the trap tubing, stop when the water reaches the top of the tee, and remove the plug (ultra-gas-series-2-users-manual, p. 7; ultra-series-4-user-manual, p. 7).
  • GV90+ Series 2: if the trap has no water, turn off the boiler ON/OFF switch and call your boiler service technician immediately (gv90-series-2-user-manual, p. 8).
  • CGa Series 3 and EG Series 7, where a condensate drain is used: the trap must be filled with water at all times the boiler runs, and if it dries out regularly, a technician should inspect it (cga-series-3-users-manual, p. 17; eg-series-7-user-manual, p. 19).

When to stop and call a professional

  • You smell gas. Do not try to light any appliance, do not touch any electrical switch or use any telephone in your building, and call your gas supplier from a phone outside the structure; if you cannot reach your gas supplier, call the fire department (eco-tec-series-3-user-manual, p. 1). The steps are at the top of every code page.
  • The boiler overheats or the gas supply does not shut off. The CGa Series 3 user’s manual says not to turn off or disconnect the electrical supply to the pump, and to shut off the gas supply at a location external to the appliance (cga-series-3-users-manual, p. 4).
  • An Ultra Series 1 or 2 shows a hard lockout. Each E code’s row in the supplement lists technician checks and part replacements (ultra-gas-series-2-control-supplement, pp. 28–32), and the supplement’s note on overrun lockouts says a service technician must troubleshoot the cause and correct it before the boiler goes back into operation (ultra-gas-series-2-control-supplement, p. 9).
  • A fault continues after the reset (eco-tec-series-3-user-manual, p. 11), or a vent or air blockage cannot be removed (eg-series-7-user-manual, p. 4).
  • The gauge stays above your series’ number, or the condensate check finds a problem (see above).
  • Carbon monoxide. The newer user’s manuals say the installer is required to confirm that at least one carbon monoxide alarm is installed in the living space before the boiler is put into operation (eco-tec-series-3-user-manual, p. 3; evergreen-series-2-user-manual, p. 3; ultra-series-4-user-manual, p. 3). Others strongly recommend a carbon monoxide detector wired on the same electrical circuit as the boiler (eco-tec-series-2-users-manual, p. 3; aquabalance-series-2-user-manual, p. 3). For Direct Exhaust units, the GV90+ Series 2 manual requires a detector in the same room and near the boiler, on the boiler’s circuit (gv90-series-2-user-manual, p. 3).
  • Once a year in any case: the ECO Tec Series 3 and Simplicity user’s manuals ask for a start-up and service at least annually by a qualified service technician (eco-tec-series-3-user-manual, p. 3; simplicity-users-manual, p. 3).

The code tables on these pages come from Weil-McLain’s boiler manuals and the Ultra Series 1 and 2 control supplement. No separate service manuals for the current series were in the public part of weil-mclain.com, and the distributor library needs a login (checked October 23, 2026). So the pages give no causes or checks beyond what those documents print.

See also

Other gas boilers: Navien boilers

Weil-McLain is a trademark of its owner. How House Works is not affiliated with or endorsed by Weil-McLain.

Sources

65 documents
  1. Weil-McLain. ECO Tec Series 3 User Manual. 550-100-598/0925. Accessed Oct 23, 2026.
  2. Weil-McLain. Ultra Gas Series 2 Control Supplement. 550-100-029/0810. Accessed Oct 23, 2026.
  3. Weil-McLain. Ultra Series 1 Boiler Manual. 550-100-009/0703. Accessed Oct 23, 2026.
  4. Weil-McLain. AquaBalance Series 2 Boiler Manual. 550-100-325/0924. Accessed Oct 23, 2026.
  5. Weil-McLain. AquaBalance Boiler Manual. 550-100-305/0118. Accessed Oct 23, 2026.
  6. Weil-McLain. AquaBalance Control Module Quick Start Guide. 550-100-316/0419. Accessed Oct 23, 2026.
  7. Weil-McLain. Simplicity Boiler Manual. 550-143-073/0125. Accessed Oct 23, 2026.
  8. Weil-McLain. Ultra Series 3-CT Boiler Manual. 550-100-090/1113. Accessed Oct 23, 2026.
  9. Weil-McLain. Ultra Series 4 Boiler Manual. 550-100-440/1025. Accessed Oct 23, 2026.
  10. Weil-McLain. EG, PEG, and EGH Control Supplement Manual. 550-142-796/0712. Accessed Oct 23, 2026.
  11. Weil-McLain. EG Control Supplement – Universal. 550-142-304/0323. Accessed Oct 23, 2026.
  12. Weil-McLain. EGH Control Supplement – Universal. 550-142-796/0915. Accessed Oct 23, 2026.
  13. Weil-McLain. CGa Series 3 Boiler Manual. 550-142-300/1025. Accessed Oct 23, 2026.
  14. Weil-McLain. CGI Series 3 Boiler Manual. 550-142-902/1016. Accessed Oct 23, 2026.
  15. Weil-McLain. CGi Series 4 Boiler Manual. 550-142-302/0124. Accessed Oct 23, 2026.
  16. Weil-McLain. CGa Boiler Manual Series 2. 550-142-900/0519. Accessed Oct 23, 2026.
  17. Weil-McLain. CGA Series 2 Boiler Manual. 550-142-779/1212. Accessed Oct 23, 2026.
  18. Weil-McLain. CGa Series 4 Boiler Manual. 550-100-223/0425. Accessed Oct 23, 2026.
  19. Weil-McLain. CGi Series 5 Boiler Manual. 550-100-629/0926. Accessed Oct 23, 2026.
  20. Weil-McLain. EG Series 7 Boiler Manual. 550-100-225/0425. Accessed Oct 23, 2026.
  21. Weil-McLain. Evergreen Series 1 Boiler. 550-100-191/G_0922. Accessed Oct 23, 2026.
  22. Weil-McLain. Evergreen Boiler Manual for Sizes 110-155. 550-100-210/D_1222. Accessed Oct 23, 2026.
  23. Weil-McLain. Evergreen Boiler Manual for Sizes 220-399. 550-100-211/0122. Accessed Oct 23, 2026.
  24. Weil-McLain. ECO Boiler Manual Series 1. 550-142-122/0513. Accessed Oct 23, 2026.
  25. Weil-McLain. ECO Series 2 Boiler Manual. 550-142-190/0120. Accessed Oct 23, 2026.
  26. Weil-McLain. WM97+ Series 2 Boiler Manual. 550-142-204/0120. Accessed Oct 23, 2026.
  27. Weil-McLain. WM97+ CT Boiler Manual Series 1. 550-142-120/1113. Accessed Oct 23, 2026.
  28. Weil-McLain. Evergreen Series 2 Boiler Manual. 550-100-579/0526. Accessed Oct 23, 2026.
  29. Weil-McLain. ECO Tec Series 2 Boiler Manual. 550-100-270/0924. Accessed Oct 23, 2026.
  30. Weil-McLain. ECO Tec Boiler Manual. 550-100-260/0520. Accessed Oct 23, 2026.
  31. Weil-McLain. GV90+ Series 2 Boiler Manual. 550-143-010/0324. Accessed Oct 23, 2026.
  32. Weil-McLain. ECO Tec Series 3 Boiler Manual. 550-100-596/1225. Accessed Oct 23, 2026.
  33. Weil-McLain. GV Series 3 Manual. 550-141-850/0699. Accessed Oct 23, 2026.
  34. Weil-McLain. GV Series 4 Manual. 550-141-856/0703. Accessed Oct 23, 2026.
  35. Weil-McLain. GV90 Manual. 550-142-054/1211. Accessed Oct 23, 2026.
  36. Weil-McLain. EGH Series 5 Control Supplement – Universal Control Systems. 550-142-796/1112. Accessed Oct 23, 2026.
  37. Weil-McLain. CGA Series 1 Manual. 550-101-009/0107. Accessed Oct 23, 2026.
  38. Weil-McLain. CGI Series 2 Manual. 550-110-710/1211. Accessed Oct 23, 2026.
  39. Weil-McLain. CGS Manual. 550-110-260/0508. Accessed Oct 23, 2026.
  40. Weil-McLain. CGS 4e Manual. 550-110-282/1108. Accessed Oct 23, 2026.
  41. Weil-McLain. CGt Boiler Manual Series 1. 550-110-290/0107. Accessed Oct 23, 2026.
  42. Weil-McLain. CGt Boiler Manual. 550-110-290/0219. Accessed Oct 23, 2026.
  43. Weil-McLain. CGI 4e Series 2 Manual. 550-110-711/1108. Accessed Oct 23, 2026.
  44. Weil-McLain. WM97+ CT Boiler Manual Series 2. 550-142-204/0119. Accessed Oct 23, 2026.
  45. Weil-McLain. ECO Tec Series 2 Users Manual. 550-100-271/1021. Accessed Oct 23, 2026.
  46. Weil-McLain. ECO Tec Users Manual. 550-100-261/0520. Accessed Oct 23, 2026.
  47. Weil-McLain. Evergreen Series 2 User Manual. 550-100-580/0325. Accessed Oct 23, 2026.
  48. Weil-McLain. Evergreen Users Manual for Sizes 110-155. 550-100-212/1220. Accessed Oct 23, 2026.
  49. Weil-McLain. Evergreen Users Manual for Sizes 220-399. 550-100-213/1220. Accessed Oct 23, 2026.
  50. Weil-McLain. Ultra Gas Series 3 Users Manual. 550-100-067/0608. Accessed Oct 23, 2026.
  51. Weil-McLain. Simplicity Users Manual. 550-143-075/0125. Accessed Oct 23, 2026.
  52. Weil-McLain. CGa Series 3 Users Manual. 550-142-301/0224. Accessed Oct 23, 2026.
  53. Weil-McLain. CGI Series 2 Users Manual. 550-110-592/0709. Accessed Oct 23, 2026.
  54. Weil-McLain. CGS Users Manual. 550-110-592/0709. Accessed Oct 23, 2026.
  55. Weil-McLain. EG, PEG, and EGH Series 4 Users Manual. 550-110-592/0709. Accessed Oct 23, 2026.
  56. Weil-McLain. EG Series 7 User Manual. 550-100-226/0425. Accessed Oct 23, 2026.
  57. Weil-McLain. AquaBalance User Manual. 550-100-306/0118. Accessed Oct 23, 2026.
  58. Weil-McLain. AquaBalance Series 2 User Manual. 550-100-326/0122. Accessed Oct 23, 2026.
  59. Weil-McLain. WM97+ CT User Manual. 550-142-086/1113. Accessed Oct 23, 2026.
  60. Weil-McLain. ECO Users Manual. 550-142-123/0513. Accessed Oct 23, 2026.
  61. Weil-McLain. GV90+ User Manual. 550-143-009/0324. Accessed Oct 23, 2026.
  62. Weil-McLain. GV Series 3 Users Manual. 550-141-812/0699. Accessed Oct 23, 2026.
  63. Weil-McLain. Ultra Series 4 User Manual. 550-100-441/1025. Accessed Oct 23, 2026.
  64. Weil-McLain. Ultra Series 4 User Manual. 550-100-441/0122. Accessed Oct 23, 2026.
  65. Weil-McLain. Ultra Gas Series 2 Users Manual. 550-100-027/0404. Accessed Oct 23, 2026.