Goodman and Amana furnace codes (LED flashes and display codes)

120 codes for 35 model series, each with the wording and source from Goodman service manuals and installation instructions.

By How House Works EditorialBased on Goodman service manuals and installation instructionsChecked against sources Updated

All Goodman codes

Meanings are quoted from Goodman service manuals and installation instructions. The "Who" column is our reading of theremedy in those documents: whether an owner can do the first checks, or the fix belongs to a licensed technician.

CodeMeaningSeriesWhoSource
E10“Grounding fault”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2037D p. 44; IOG-2040D p. 39; IOG-2035D p. 32; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2038E p. 50; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 46; RS6621007R3 p. 34; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
E10“Grounding fault Poor neutral connection”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 42; RS6612302 p. 32; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 46; IOG-2016A p. 36; IOG-2017H p. 44; IOG-2034A p. 35
E10“Grounding Error”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E11“Open roll out switch”GR9S92 / GR9S96 / GD9S96, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 43; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; RS6621305 p. 45; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 46; RS6612014R3 p. 62; IOG-2023E p. 31; IOG-2016A p. 36; IOG-2017H p. 44; IOG-2034A p. 35
E11“Open rollout switch.”GR9S92 / GR9S96 / GD9S96, GR9S80 / GD9S80 / AR9S80 / AD9S80, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVM97*BA / GCVM97TechnicianIOG-2037D p. 44; IOG-2035D p. 32; IOG-2049 p. 44; IOG-2038E p. 51; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; RS6621303 p. 36; RS6621007R3 p. 34; RS6612023R2 p. 43; RS6612015R8 p. 56
E11“Rollout Switch Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
E11“Burner limit switch circuit is open”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 32; RS6621302 p. 29; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E11“Open burner box limit switch circuit.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 46
E12“Redundant relay open alarm”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*U, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 46; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E12“Redundant Relay Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
E12“Reduntent relay open alarm”A/GR9S96*U* Ultra-Low NOxTechnicianRS6612302 p. 32
E13“Redundant relay stuck closed alarm”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*U, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 47; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E13“Redundant Relay Stuck Closed”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
E13“Reduntent relay stuck closed alarm”A/GR9S96*U* Ultra-Low NOxTechnicianRS6612302 p. 32
E14“External Flash Fault”*RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2042A p. 47
E15“Return Air Temperature Sensor Circuit is Open (External)”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 46; IOG-2023E p. 31; IOG-2017H p. 45
E16“Return Air Temperature Sensor Circuit is Shorted (External)”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 46; IOG-2023E p. 31; IOG-2017H p. 45
E17“Supply Air Temperature Sensor Circuit is Open (External)”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 47; IOG-2023E p. 32; IOG-2017H p. 45
E18“Supply Air Temperature Sensor Circuit is Shorted (External)”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 47; IOG-2023E p. 32; IOG-2017H p. 45
E19“Onboard return air temperature sensor is unplugged”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 47; IOG-2023E p. 32; IOG-2017H p. 45
E1A“Onboard return air temperature sensor is shorted”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 47; IOG-2015L p. 47; IOG-2023E p. 32; IOG-2017H p. 45
E1b“Analog Pressure Sensor Reference Error.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*U, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 47; IOG-2034A p. 34
E1b“APS reference error”A/GR9S96*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 32; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E1C“APS null error”A/GR9S96*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 32; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E1C“Analog Pressure Sensor null error.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 47
E1c“Analog Pressure Sensor Null Error.”*MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2034A p. 34
E1d“Analog Pressure Sensor Span Error.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*U, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2042A p. 47; IOG-2034A p. 34
E1d“APS span error”A/GR9S96*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 33; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E1E“APS pressure error”A/GR9S96*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 33; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E1E“Analog Pressure Sensor pressure error.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 40; IOG-2042A p. 48
E1e“Analog Pressure Error (Blocked Vent Error)”*MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2034A p. 34
E1F“APS input error”A/GR9S96*U* Ultra-Low NOx, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612302 p. 33; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
E1F“Analog Pressure Sensor input error.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 40; IOG-2042A p. 48
E1f“Analog Pressure Sensor, Input Error”*MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2034A p. 34
EA0“R-32 sensor has detected a refrigerant leak and furnace is in mitigation mode.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48; RS6612023R2 p. 44
EA0“A2L Refrigerant Leakage Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40
EA1“R-32 sensor has detected a fault and furnace is in mitigation mode.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48; RS6612023R2 p. 44
EA1“A2L Sensor Internal Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40
EA1“R-32 sensor has detected a fault and the furnace is in mitigation mode.”GRVT80 / GDVT80 / ARVT80 / ADVT80TechnicianRS6621305 p. 47
EA2“The furnace control board has detected an issue with the internal A2L relay and is running mitigation mode.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48
EA2“A2L relay in the furnace control board has detected a fault and furnace is in mitigation mode.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianRS6612305 p. 44; RS6612306 p. 44; RS6621303 p. 40; RS6612023R2 p. 44
EA2“A2L Relay Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40
EA2“A2L relay in the furnace control board has detected a fault and the furnace is in mitigation mode.”GRVT80 / GDVT80 / ARVT80 / ADVT80TechnicianRS6621305 p. 47
EAF“Furnace has lost communication with the R-32 sensor and the furnace is in mitigation mode.”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2037D p. 45; IOG-2040D p. 40; IOG-2035D p. 33; IOG-2039F p. 34; IOG-2050A p. 41; IOG-2038E p. 52; IOG-2036D p. 33; IOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48; RS6612023R2 p. 44
EAF“A2L Sensor Comm Alarm”
What to check
GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40
EAL“R-32 sensor has detected a refrigerant leak and furnace is in mitigation mode.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 45; IOG-2040D p. 40; IOG-2035D p. 33; IOG-2039F p. 34; IOG-2050A p. 41; IOG-2038E p. 52; IOG-2036D p. 33
EAr“The furnace control board has detected an issue with the internal A2L relay and is running mitigation mode.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 45; IOG-2040D p. 40; IOG-2035D p. 33; IOG-2039F p. 34; IOG-2050A p. 41; IOG-2038E p. 52; IOG-2036D p. 33
EAr“A2L relay in the furnace control board has detected a fault and furnace is in mitigation mode.”GR9S80 / GD9S80 / AR9S80 / AD9S80TechnicianIOG-2035D p. 33
Ear“A2L relay in the furnace control board has detected a fault and the furnace is in mitigation mode.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037A p. 43; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37
EAS“R-32 sensor has detected a fault and furnace is in mitigation mode.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 45; IOG-2040D p. 40; IOG-2035D p. 33; IOG-2039F p. 34; IOG-2050A p. 41; IOG-2038E p. 52; IOG-2036D p. 33
EAS“R-32 sensor has detected a fault and the furnace is in mitigation mode.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037A p. 43; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37
Eb0“Circulator blower motor is not running when it should be running”GRVT80 / GDVT80 / ARVT80 / ADVT80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 45; IOG-2015L p. 45; RS6612014R3 p. 62; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb0“Blower Motor Not Running”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb0“Circulator blower motor not running when it should be running.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; RS6612023R2 p. 40
Eb1“Integrated control module has lost communications with circulator blower motor”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb1“Blower Communication Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb1“Integrated control module has lost communications with circulator blower.”GMVM97*BA / GCVM97TechnicianRS6612015R8 p. 57
Eb2“Circulator blower motor horse power in shared data set does not match circulator blower motor horse power.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb2“Blower Motor HP/ID Mismatch”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb2“Circulator blower motor horsepower in shared data set does not match circulator blower motor horsepower.”GMVM97*BA / GCVM97TechnicianRS6612015R8 p. 57
Eb3“Circulator blower motor is operating in a power, temperature, or speed limiting condition”GRVT80 / GDVT80 / ARVT80 / ADVT80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 46; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb3“Blower Motor Operating in Power, Temperature, or Speed Limit”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb3“Circulator blower motor is operating in a power, temperature or speed limiting condition.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; RS6612023R2 p. 40
Eb4“Circulator blower motor senses a loss of rotor control”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb4“Blower Motor Current Trip or Lost Rotor”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb5“Circulator blower motor fails to start 10 consecutive times”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb5“Blower Motor Locked Rotor”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015 p. 60
Eb6“Circulator blower motor shuts down for over or under voltage condition.”GRVT80 / GDVT80 / ARVT80 / ADVT80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 47; IOG-2015L p. 45; RS6612014R3 p. 63; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb6“Over/Under Voltage Trip or Over Temperature Trip”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb6“Circulator blower motor shuts down due to over or under voltage condition.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BBTechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; RS6612023R2 p. 41
Eb7“Circulator blower motor does not have enough information to operate properly.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; RS6612023R2 p. 41; RS6612014R3 p. 63; RS6621009R1 p. 52; RS6612015R8 p. 58
Eb7“Incomplete Parameters Sent to Motor”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Eb7“Circulator blower motor lacks information to operate properly”GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2015L p. 45; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
Eb9“Airflow is lower than demanded”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 50; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; IOG-2015L p. 46; RS6612014R3 p. 63; IOG-2023E p. 31; IOG-2016A p. 36; IOG-2017H p. 44; IOG-2034A p. 34
Eb9“Inadequate Airflow”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EbF“Inducer communication alarm”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*U, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 40; IOG-2042A p. 48; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EbF“Inducer Comm Error”GMVM97*BA / GCVM97TechnicianIOG-2017H p. 47
EbF“Inducer communicating error.”GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianIOG-2045A p. 52
EbL“Main blower motor is consuming very little current after heat on delay, below an expected value”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80TechnicianIOG-2037A p. 43; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29
EbL“Circulator blower motor is consuming very little current after heat ON delay - below expected value.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31
EbL“Low circulator current”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EbL“Main blower motor is consuming very little current after heat on delay , below an expected value”GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2027E p. 47; IOG-2026B p. 31
EbL“Circulator blower motor current after heat ON delay is lower than expected value.”GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianRS6621007R3 p. 33
EbS“Blower Motor Locked Rotor”GMVM97*BA / GCVM97TechnicianRS6612015R8 p. 50
EbU“Main blower motor is consuming too much current during inducer pre-purge, above an expected value.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037A p. 43; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31
EbU“Circulator blower motor is consuming too much current during inducer pre-purge is higher than expected value.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31
EbU“Circulator current unexpected”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EbU“Circulator blower motor current during inducer pre-purge is higher than expected value.”GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianRS6621007R3 p. 33
EC1“Network Communication Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015 p. 60
EC2“E-Module Network Communication Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EC3“Bluetooth Module Network Communication Alarm”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EC4“Equipment Relay Module Missing”GMVC96*BA, GMVM97*BA / GCVM97TechnicianRS6612014 p. 61; RS6612015 p. 60
EC5“Accessory Relay Module Missing”GMVC96*BA, GMVM97*BA / GCVM97TechnicianRS6612014 p. 61; RS6612015 p. 60
ECF“Gas Valve Stepper Motor Comm Error”GMVM97*BA / GCVM97TechnicianIOG-2017H p. 47
ECF“Gas valve stepper motor communication error.”GRVM97 / GDVM97 / ARVM97 / ADVM97TechnicianIOG-2045A p. 52
ECI“Network Communication Alarm”GMVM97*BA / GCVM97TechnicianRS6612015R8 p. 50
Ed0“Data not yet on network”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; IOG-2015L p. 47; RS6612014R3 p. 56; IOG-2023E p. 32; IOG-2016A p. 36; RS6612015R8 p. 50; IOG-2034A p. 35
Ed0“No shared data”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2040D p. 38; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
Ed0“Equipment lacks shared data”GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*ACTechnicianIOG-2015L p. 45; IOG-2023E p. 30
Ed1“Invalid memory card data”GRVT80 / GDVT80 / ARVT80 / ADVT80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 45; IOG-2015F p. 48; RS6612014R3 p. 62; IOG-2023E p. 32; IOG-2016A p. 36; IOG-2017F p. 47; IOG-2034A p. 35
Ed1“Invalid shared data”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; IOG-2015L p. 47; IOG-2017H p. 46; IOG-2025G p. 40
Ed1“Invalid Data on Network”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Ed4“Invalid External Shared Data”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Ed5“Invalid Downloaded Firmware”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015 p. 60
Ed6“Un-Recognized Data ID”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
Ed8“Invalid Call (check ODS setting)”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31
EdS“Invalid Downloaded Firmware”GMVM97*BA / GCVM97TechnicianRS6612015R8 p. 50
EE0“Furnace lockout due to an excessive number of ignition “retries” (3 total)”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UOwner checks, then technicianIOG-2037A p. 41; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6612304 p. 27; RS6621304 p. 35; RS6621305 p. 43; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2032C p. 37; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 48; RS6612014R3 p. 60; IOG-2023E p. 33; IOG-2016A p. 36; IOG-2017H p. 46; IOG-2034A p. 35; RS6612017R4 p. 30; RS6621006R4 p. 33
EE0“Furnace lockout due to excessive number of ignition "retries" (3 total).”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBOwner checks, then technicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; RS6621007R3 p. 33; RS6612023R2 p. 41
EE0“Lockout Due to Excessive Retries or Recycles”
What to check
GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97Owner checks, then technicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE1“Pressure switch circuit is closed at start of heating cycle”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 41; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6612304 p. 27; RS6621304 p. 35; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2034A p. 35
EE1“Low stage pressure switch circuit is closed at start of heating cycle”GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 43; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 48; RS6612014R3 p. 60; IOG-2023E p. 33; IOG-2016A p. 36; IOG-2017H p. 46; RS6612019R3 p. 32
EE1“Low-stage pressure switch circuit closed at start of heating cycle.”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2038E p. 49; IOG-2036D p. 31; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; RS6621007R3 p. 33; RS6612023R2 p. 41
EE1“Pressure switch circuit closed at start of heating cycle.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2042A p. 46
EE1“Draft Inducer pressure switch circuit is closed at start of heating cycle”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 37; RS6612017R4 p. 30; RS6621006R4 p. 33
EE2“Pressure switch circuit is not closed”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 41; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6612304 p. 27; RS6621304 p. 35; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2034A p. 35
EE2“Low stage pressure switch circuit is not closed”GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6621305 p. 43; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 48; RS6612014R3 p. 60; IOG-2023E p. 33; IOG-2016A p. 36; IOG-2017H p. 46; RS6612019R3 p. 32
EE2“Low-stage pressure switch circuit open.”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2038E p. 50; IOG-2036D p. 31; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; RS6621007R3 p. 33; RS6612023R2 p. 42
EE2“Low Stage Pressure Switch Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE2“Pressure switch circuit open.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2042A p. 46
EE2“Draft Inducer pressure switch circuit is not closed”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 37; RS6612017R4 p. 30; RS6621006R4 p. 33
EE3“Primary limit circuit is open”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2037A p. 41; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6612304 p. 27; RS6621304 p. 35; RS6621305 p. 43; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2032C p. 37; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 48; RS6612014R3 p. 60; IOG-2023E p. 33; IOG-2016A p. 36; IOG-2017H p. 46; IOG-2034A p. 35; RS6612017R4 p. 30; RS6621006R4 p. 33
EE3“Primary limit circuit open.”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 39; IOG-2038E p. 50; IOG-2036D p. 31; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; RS6621007R3 p. 33; RS6612023R2 p. 42
EE3“Open High Limit Switch”
What to check
GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE4“Flame sensed with no call for heat”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 39; IOG-2038E p. 50; IOG-2036D p. 31; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2032C p. 37; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 48; RS6612014R3 p. 61; IOG-2023E p. 33; IOG-2016A p. 37; IOG-2017H p. 46; IOG-2034A p. 36; RS6612017R4 p. 30; RS6621006R4 p. 33
EE4“Flame Detected When no Flame Should be Present”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE5“Open fuse Short in low voltage wiring”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2037A p. 42; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6621304 p. 36; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2032C p. 37; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015F p. 49; IOG-2023E p. 33; IOG-2016A p. 37; IOG-2017H p. 46; IOG-2034A p. 36; RS6612017R4 p. 30; RS6621006R4 p. 33
EE5“Open fuse.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2038E p. 50; IOG-2036D p. 32; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; RS6621007R3 p. 33; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE5“Open fuse. Short in low voltage wiring.”GMVC96*BB / GCVC96*BBTechnicianIOG-2015L p. 48
EE6“Flame sense micro amp signal is low”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037D p. 44; IOG-2040D p. 39; IOG-2035D p. 32; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2038E p. 50; IOG-2036D p. 32; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46; RS6621007R3 p. 33; IOG-2015L p. 48; RS6612014R3 p. 61; IOG-2023E p. 33; IOG-2016A p. 37; IOG-2017H p. 47; IOG-2034A p. 36
EE6“Flame sense micro amp signal is minimal”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2037A p. 42; RS6612302 p. 32; RS6621302 p. 28; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 36; IOG-2029D p. 40; IOG-2030B p. 28; IOG-2032C p. 37; IOG-2027E p. 46; IOG-2026B p. 30; RS6612017R4 p. 30; RS6621006R4 p. 33
EE6“Low Flame Signal”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE7“Problem with igniter circuit”A/GR9S80*U* Ultra-Low NOx, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, *M9S96*U; *M9S80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UTechnicianRS6621302 p. 28; IOG-2038E p. 50; IOG-2036D p. 32; RS6612305 p. 42; RS6621305 p. 44; RS6612306 p. 43; RS6621303 p. 35; IOG-2032C p. 37; RS6621007R3 p. 33; IOG-2015L p. 49; RS6612014R3 p. 61; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2017H p. 47; IOG-2034A p. 36; RS6612017R4 p. 30; RS6621006R4 p. 33
EE7“Problem with ignitor circuit.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 39; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; IOG-2042A p. 46
EE7“Igniter Fault or Improper Grounding”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EE7“Problen with igniter circuit.”GMVM97*BA / GCVM97TechnicianRS6612015 p. 65
EE8“High stage pressure switch circuit is closed at start of heating cycle.”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6612304 p. 28; RS6621304 p. 36; RS6621305 p. 44; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 49; RS6612014R3 p. 61; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2017H p. 47; RS6612019R3 p. 33
EE8“High-stage pressure switch circuit closed at start of heating cycle.”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2038E p. 50; IOG-2036D p. 32; IOG-2044B p. 50; IOG-2043B p. 35; IOG-2045A p. 50; RS6621007R3 p. 34; RS6612023R2 p. 42
EE9“High stage pressure switch circuit is not closed”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6612304 p. 28; RS6621304 p. 36; RS6621305 p. 44; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 49; RS6612014R3 p. 61; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2017H p. 47; RS6612019R3 p. 33
EE9“High-stage pressure switch circuit open.”GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2038E p. 50; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 35; IOG-2045A p. 51; RS6621007R3 p. 34; RS6612023R2 p. 42
EE9“High Stage Pressure Switch Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEA“Polarity of 115 volt AC is reversed Poor unit ground”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, *M9S96*U; *M9S80*U, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, *MVS80*U ; CCVS80; *MVS96; CCVS96, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2037A p. 42; RS6612302 p. 32; RS6621302 p. 29; RS6621304 p. 36; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2032C p. 38; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 49; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2034A p. 36; RS6612017R4 p. 31; RS6621006R4 p. 34
EEA“Polarity if 115 volt AC is reversed.”GR9S92 / GR9S96 / GD9S96, GR9S80 / GD9S80 / AR9S80 / AD9S80, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianIOG-2037D p. 44; IOG-2035D p. 32; IOG-2049 p. 44; IOG-2038E p. 51; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; RS6621007R3 p. 34; RS6612023R2 p. 44
EEA“Reversed Line Polarity”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEA“Polarity of 115 volt AC is reversed”GR9S92 / GR9S96 / GD9S96, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*ACTechnicianRS6612301 p. 37; RS6612304 p. 28; RS6621305 p. 44; RS6612023 p. 62; RS6612014R3 p. 61; RS6621009R1 p. 49
EEA“Polarity of 120 volt AC is reversed.”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 39; IOG-2039F p. 33; IOG-2050A p. 40; IOG-2042A p. 48
EEA“Polarity of 115 volt AC is reversed. Poor unit ground.”GMVM97*BA / GCVM97TechnicianIOG-2017H p. 47
EEA“Polarity if 120 volt AC is reversed.”*RVS96*U & CDVS96*U; *RVS80*UTechnicianRS6621303 p. 39
EEb“Gas valve is not energized when it should be”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 42; RS6612302 p. 32; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 36; RS6612305 p. 43; RS6621305 p. 44; RS6612306 p. 44; RS6621303 p. 39; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 49; RS6612014R3 p. 61; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2017H p. 47; IOG-2034A p. 36
EEb“Integrated Control Board is not energizing the gas valve when it should be on.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 44; IOG-2040D p. 39; IOG-2035D p. 32; IOG-2039F p. 33; IOG-2050A p. 40; IOG-2038E p. 51; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 51; IOG-2042A p. 48
EEb“Internal Gas Valve Error”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEb“Gas valve is energized when it should not be”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EEC“Gas valve is energized when it should not be”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 42; RS6612302 p. 32; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; RS6612305 p. 43; RS6621305 p. 45; RS6612306 p. 44; RS6621303 p. 39; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 49; RS6612014R3 p. 62; IOG-2023E p. 34; IOG-2016A p. 37; IOG-2017H p. 47; IOG-2034A p. 36
EEC“Gas valve is energized when it should be off.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 44; IOG-2040D p. 39; IOG-2035D p. 32; IOG-2039F p. 34; IOG-2050A p. 40; IOG-2038E p. 51; IOG-2036D p. 32; IOG-2044B p. 51; IOG-2043B p. 36; IOG-2045A p. 52; IOG-2042A p. 48
EEC“External Gas Valve Error”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEC“Gas valve is not energized when it should be”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EEd“Aux limit switch open (blower compartment)”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianRS6612305 p. 43; RS6621305 p. 45; RS6612306 p. 44; RS6621303 p. 39; IOG-2015L p. 49; RS6612014R3 p. 62; RS6621009R1 p. 50; IOG-2016A p. 38; RS6612015R8 p. 56; IOG-2034A p. 36
EEd“Auxiliary limit switch open (blower compartment).”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2040D p. 40; IOG-2039F p. 34; IOG-2050A p. 40; IOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48
EEd“Auxiliary Limit Switch Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEd“Auxiliary limit switch (blower compartment) circuit is open”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EEd“Auxiliary limit circuit is open”A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOxTechnicianRS6612302 p. 32; RS6621302 p. 29
EEE“Furnace control board has detected an internal fault.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 44; IOG-2040D p. 40; IOG-2035D p. 32; IOG-2039F p. 34; IOG-2050A p. 40; IOG-2038E p. 51; IOG-2036D p. 32; IOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48
EEE“Internal Faults or IRQ Loss in Control Board”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037A p. 43; RS6612302 p. 31; RS6621302 p. 28; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31
EEE“Internal Control Fault”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *M9S96*U; *M9S80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97, *MES96*U, GMES80*U / AMES80*UTechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; IOG-2032C p. 37; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50; RS6612017R4 p. 30; RS6621006R4 p. 33
EEE“Internal Faults or IRQ Loss in integrated control board.”GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianRS6621007R3 p. 34
EEF“Aux switch (condensate switch) open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2044B p. 52; IOG-2043B p. 37; IOG-2045A p. 52; IOG-2042A p. 48; RS6612023R2 p. 44; RS6612014R3 p. 62; RS6621009R1 p. 50; IOG-2016A p. 38; RS6612015R8 p. 56; IOG-2034A p. 36
EEF“Condensate Switch Open”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVM97*BA / GCVM97TechnicianRS6612305 p. 39; RS6621305 p. 42; RS6612306 p. 40; RS6612023R2 p. 36; RS6612014R3 p. 56; RS6621009R1 p. 44; RS6612015R8 p. 50
EEF“Aux limit switch (condensate switch) open”GMVC96*BB / GCVC96*BBTechnicianIOG-2015L p. 49
EEH“TWIN Error”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037A p. 43; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31
EEH“Error with Twinning function.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 44; IOG-2040D p. 40; IOG-2035D p. 32; IOG-2039F p. 34; IOG-2050A p. 41; IOG-2038E p. 51; IOG-2036D p. 33
EEH“Twinning error”*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UTechnicianIOG-2032C p. 38; RS6612017R4 p. 31; RS6621006R4 p. 34
EEJ“Inducer relay Error”GR9S92 / GR9S96 / GD9S96, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037A p. 43; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31
EEJ“Inducer motor relay error.”GR9S92 / GR9S96 / GD9S96, GR9S80 / GD9S80 / AR9S80 / AD9S80, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 44; IOG-2035D p. 32; IOG-2049 p. 45; IOG-2038E p. 51; IOG-2036D p. 33
EEL“Problem with igniter circuit”GR9S92 / GR9S96 / GD9S96, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037A p. 42; RS6612301R2 p. 39; RS6612304 p. 28; RS6621304 p. 36; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 46; IOG-2026B p. 30
EEL“Problem with ignitor circuit.”GR9S92 / GR9S96 / GD9S96, GR9S80 / GD9S80 / AR9S80 / AD9S80, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80TechnicianIOG-2037D p. 45; IOG-2035D p. 32; IOG-2049 p. 45; IOG-2038E p. 52; IOG-2036D p. 33
EEn“Ignitor Open”GR9S92 / GR9S96 / GD9S96, GR9S80 / GD9S80 / AR9S80 / AD9S80, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianIOG-2037D p. 45; IOG-2035D p. 33; IOG-2049 p. 45; IOG-2038E p. 52; IOG-2036D p. 33; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31
EEn“Igniter open.”GR9S92 / GR9S96 / GD9S96, VR9S80/VD9S80, GM9C80 / GC9C80 / AM9C80 / AC9C80TechnicianRS6612301R2 p. 39; RS6621007R3 p. 34
IdL“Normal operation”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96Owner can checkIOG-2037A p. 41; RS6612302 p. 31; RS6621301 p. 34; RS6621302 p. 28; RS6612304 p. 27; RS6621304 p. 35; RS6621305 p. 43; IOG-2029D p. 39; IOG-2030B p. 28; IOG-2027E p. 46; IOG-2026B p. 30; IOG-2015L p. 45; RS6612014R3 p. 60; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
IdL“Idle”
What to check
GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*U, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBOwner can checkIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31; IOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45; RS6621007R3 p. 33; RS6612023R2 p. 40
IdL“Stand-by Mode Normal Operation”
What to check
*M9S96*U; *M9S80*U, *MES96*U, GMES80*U / AMES80*UOwner can checkIOG-2032C p. 37; RS6612017R4 p. 30; RS6621006R4 p. 33
None“No 115 power to furnace or no 24 volt power to integrated control module.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT80 / GDVT80 / ARVT80 / ADVT80, GM9S92 / GM9S96 / GC9S96, GM9S80 / GC9S80 / AM9S80 / AC9S80 / VM9S80 / VC9S80, GM9C96 / GC9C96 / AM9C96 / AC9C96, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BB, GMVC96*BA, GMVC80*AC / GCVC80*AC / ACVC80*AC / AMVC80*AC, GMVC8 / AMVC8 / ADVC8; ACVC8 / GCVC8, GMVM97*BA / GCVM97, *MVS80*U ; CCVS80; *MVS96; CCVS96TechnicianIOG-2037A p. 42; RS6612302 p. 33; RS6621302 p. 29; RS6612301 p. 37; RS6612304 p. 28; RS6621304 p. 37; RS6621305 p. 43; IOG-2029D p. 40; IOG-2030B p. 29; IOG-2027E p. 47; IOG-2026B p. 31; IOG-2015L p. 45; RS6612014R3 p. 60; IOG-2023E p. 30; IOG-2016A p. 35; IOG-2017H p. 44; IOG-2033A p. 29
nonE“No 120VAC power to furnace or no 24 volt power to integrated control module.”GR9S92 / GR9S96 / GD9S96, A/GR9S96*U* Ultra-Low NOx, GR9S80 / GD9S80 / AR9S80 / AD9S80, A/GR9S80*U* Ultra-Low NOx, VR9S80/VD9S80, GR9T96 / GD9T96 / AR9T96 / AD9T96, GR9T80 / GD9T80 / AR9T80 / AD9T80, GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVT80 / GDVT80 / ARVT80 / ADVT80, GRVM97 / GDVM97 / ARVM97 / ADVM97, *RVS96*U & CDVS96*U; *RVS80*UTechnicianIOG-2037D p. 43; IOG-2040D p. 38; IOG-2035D p. 31; IOG-2039F p. 32; IOG-2050A p. 38; IOG-2038E p. 49; IOG-2036D p. 31; IOG-2044B p. 49; IOG-2043B p. 34; IOG-2045A p. 49; IOG-2042A p. 45
nonE“No 115v power to furnace or no 24 volt power to integrated control module.”GRVT96 / GDVT96 / ARVT96 / ADVT96, GRVM97 / GDVM97 / ARVM97 / ADVM97, GM9C80 / GC9C80 / AM9C80 / AC9C80, GMVC96*BB / GCVC96*BBTechnicianRS6612305 p. 40; RS6612306 p. 41; RS6621007R3 p. 33; RS6612023R2 p. 40
nonE“No 120v power to furnace or no 24 volt power to integrated control module.”*RVS96*U & CDVS96*U; *RVS80*UTechnicianRS6612303 p. 34
1 flash“Furnace lockout due to an excessive number of ignition “retries” (3 total).”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8Owner checks, then technicianIOG-2020J p. 40; IOG-2021H p. 29; IOG-2009Q p. 42; RS6612004R2 p. 49; RS6612006R7 p. 43; RS6612007R4 p. 41; RS6612003R2 p. 54; RS6612005R1 p. 49; RS6621001R2 p. 35
1 flash“Furnace lockout due to an excessive number of ignition attempts. (3 total)”
What to check
GMS8 / AMS8 / GDS8 / ADSS8Owner checks, then technicianRS6612006R7 p. 45
2 flashes“Pressure switch circuit is closed.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 40; IOG-2021H p. 29; IOG-2009Q p. 42; RS6612004R2 p. 49; RS6612006R7 p. 43; RS6612007R4 p. 41; RS6612003R2 p. 54; RS6612005R1 p. 49; RS6621001R2 p. 35
3 flashes“Pressure switch circuit not closed.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 40; IOG-2021H p. 29; IOG-2009Q p. 42; RS6612004R2 p. 49; RS6612006R7 p. 43; RS6612007R4 p. 41; RS6612003R2 p. 54; RS6612005R1 p. 49; RS6621001R2 p. 35
4 flashes“Primary or auxiliary limit circuit is open.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8TechnicianIOG-2020J p. 41; IOG-2021H p. 30; IOG-2009Q p. 43; RS6612004R2 p. 50; RS6612006 p. 39
4 flashes“Primary limit circuit is open.”
What to check
GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMS8 / AMS8 / GDS8 / ADSS8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianRS6621003 p. 37; RS6612006R7 p. 44; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
5 flashes“Flame sensed with no call for heat.”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 41; IOG-2021H p. 30; IOG-2009Q p. 43; RS6612004R2 p. 50; RS6612006R7 p. 44; RS6612007R4 p. 42; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
6 flashes“Rollout limit open.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 41; IOG-2021H p. 30; IOG-2009Q p. 43; RS6612006R7 p. 46; RS6612007R4 p. 42; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
6 flashes“Rollout limit circuit is open.”
What to check
GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8TechnicianRS6621003 p. 37; RS6612012 p. 43; RS6612004R2 p. 50; RS6612006R7 p. 44
6 flashes“Rollout limit circuit is open/Control board fuse open.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMSS9* / GCSS9* / AMSS9* / ACSS9*TechnicianRS6612016 p. 44; RS6612012R8 p. 45
7 flashes“Flame sense microamp signal is low.”
What to check
GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 41; IOG-2021H p. 30; IOG-2009Q p. 43; RS6612004R2 p. 50; RS6612006R7 p. 44; RS6612007R4 p. 42; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
8 flashes“Problem with igniter circuit.”GMSS9* / GCSS9* / AMSS9* / ACSS9*, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2009Q p. 43; RS6612006R7 p. 47; RS6612007R4 p. 42; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
8 flashes“Igniter Relay Fault”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80TechnicianIOG-2020J p. 41; IOG-2021H p. 30
9 flashes“Twinning Fault”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*TechnicianIOG-2020J p. 42; IOG-2021H p. 31; IOG-2009Q p. 43
10 flashes“Open Fuse / No 24V power to integrated control module”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80TechnicianIOG-2020J p. 42; IOG-2021H p. 31
11 flashes“Igniter Open”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80TechnicianIOG-2020J p. 42; IOG-2021H p. 31
12 flashes“Inducer Relay Fault”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80TechnicianIOG-2020J p. 42; IOG-2021H p. 31
Red 1 flash“Flame sensed when no flame should be present”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Red 1 flash“Furnace lockout due to an excessive number of ignition attempts. (3 total retries)”*MES96*U, GMES80*U / AMES80*UOwner checks, then technicianRS6612017 p. 20; RS6621006 p. 16
Red 2 flashes“Pressure switch stuck closed”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Red 2 flashes“Pressure sensor indicates pressure reading when it should be zero.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 20; RS6621006 p. 16
Red 3 double flashes“Second stage pressure switch stuck open”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 3 flashes“Low fire pressure switch stuck open”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Red 3 flashes“Inducer not making pressure setting.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 20; RS6621006 p. 16
Red 4 flashes“Open limit circuit, main limit, aux limit, or roll out switch”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 4 flashes“Primary limit insert; or aux limit circuit is open.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 20; RS6621006 p. 16
Red 5 flashes“Limit & rollout circuit open for 15 minutes. Open control board fuse or rollout switch”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 5 flashes“Flame sensed with no call for heat.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 20; RS6621006 p. 16
Red 6 flashes“Pressure switch cycling lockout, pressure switch has opened 5 times in the same heating cycle”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner checks, then technicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 6 flashes“Burner temperature limit switch open.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Red 7 flashes“Lockout - excessive retries from flame not being proven during trial for ignition”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner checks, then technicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 7 flashes“Gas valve circuit shorted.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Red 8 flashes“Lockout - excessive recycles from flame proving being lost after being proven”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner checks, then technicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 8 flashes“Excessive inducer motor speed or drive signal is required.”GMES80*U / AMES80*UTechnicianRS6621006 p. 17
Red 9 flashes“Improper grounding or reverse polarity”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 10 flashes“Gas valve current detected with no call for heat”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 11 flashes“Open limit switch circuit for more than 5 minutes”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red 12 flashes“Control board igniter relay not energizing igniter”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Amber 1 flash“Normal operation with low stage call for heat (W1)”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Amber 1 flash“Low flame sense”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Amber 2 flashes“Normal operation with high or single stage call for heat”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Amber 2 flashes“ID plug failure”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Amber 3 flashes“W2 call present without W1”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Amber 3 flashes“Integrated control module fuse is blown.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Amber 4 flashes“Ylo or Y call present without G”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Green 1 flash“Normal operation with low stage call for cooling (Ylo & G)”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Green 1 flash“Call for heating.”*MES96*U, GMES80*U / AMES80*UOwner can checkRS6612017 p. 21; RS6621006 p. 17
Green 2 flashes“Normal operation with high or single stage call for cooling (Y & G)”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Green 2 flashes“Call for cooling.”*MES96*U, GMES80*U / AMES80*UOwner can checkRS6612017 p. 21; RS6621006 p. 17
Green 3 flashes“Continuous fan operation.”*MES96*U, GMES80*U / AMES80*UOwner can checkRS6612017 p. 21; RS6621006 p. 17
Amber rapid“Low flame sense current”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
Amber steady on“OEM test mode”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Green rapid flash“Furnace is receiving a call for fan (24 volts on G terminal”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Green rapid flashes“Clear error history.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 21; RS6621006 p. 17
Green solid on“Furnace is not receiving a call”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80Owner can checkIOG-2011U p. 54; RS6621005R1 p. 28
Green steady on“Normal operation, idle/ standby.”*MES96*U, GMES80*U / AMES80*UOwner can checkRS6612017 p. 21; RS6621006 p. 17
LED off“No 115 volt power to furnace, or no 24 volt power to integrated control module.”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 40; IOG-2021H p. 29; IOG-2009Q p. 42; RS6612004R2 p. 49; RS6612006R7 p. 43; RS6612007R4 p. 41; RS6612003R2 p. 54; RS6612005R1 p. 49; RS6621001R2 p. 35
LED off“Defective disconnect switch”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 54; RS6621005R1 p. 28
LED off“No 120-volt power to furnace or 24-volt power to integrated control module.”*MES96*U, GMES80*U / AMES80*UTechnicianRS6612017 p. 20; RS6621006 p. 16
LED steady on“Normal Operation”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8Owner can checkIOG-2020J p. 40; IOG-2021H p. 29; IOG-2009Q p. 42; RS6612004R2 p. 49; RS6612006R7 p. 43; RS6612007R4 p. 41; RS6612003R2 p. 54; RS6612005R1 p. 49; RS6621001R2 p. 35
Rapid flash“Polarity of 115 or 24 volt power is reversed.”GMES9* / GCES9* / AMES9* / ACES9* / VMES9* / VCES9*, GMES80 / GCES80 / AMES80 / ACES80 / VMES80 / VCES80, GMSS9* / GCSS9* / AMSS9* / ACSS9*, GKS9 / AKSS92, GMS8 / AMS8 / GDS8 / ADSS8, GMH8 / AMH8 / GDH8 / ADSH8, GMH95 / AMH95 / GCH95 / ACSH96, GME95 / AMEH96, GME8 / AMEH8TechnicianIOG-2020J p. 42; IOG-2021H p. 31; IOG-2009Q p. 43; RS6612004R2 p. 50; RS6612006R7 p. 44; RS6612007R4 p. 42; RS6612003R2 p. 55; RS6612005R1 p. 50; RS6621001R2 p. 36
Red rapid flash“Twinning error”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29
Red solid on“Control board internal fault”GMEC96 / AMEC96, GMEC80 / GCEC80 / AMEC80 / ACEC80TechnicianIOG-2011U p. 55; RS6621005R1 p. 29

How to read a Goodman code

These pages cover Goodman and Amana gas furnaces. Goodman’s service manuals and installation instructions cover both brands, with titles such as “Goodman Brand GR9T96/GD9T96 & Amana Brand AR9T96/AD9T96” RS6612304, p. 1. Amana’s own literature library lists only product specifications, brochures and warranty certificates for gas furnaces (amana-hac.com, checked October 19, 2026).

How the code is shown depends on the control board. Goodman’s code tables are tied to the series named on each document’s cover; they do not say which board a given model number has.

  • A single LED that flashes a count. The owner’s manual has you look through the blower compartment sight glass and record the number of flashes seen in sequence HIG-2002A, p. 8. The GMSS9 service manual says to count the flashes between pauses through the observation window in the blower access door RS6612012, p. 31. On these boards a steady light is normal operation. No light means no 115 volt power to the furnace, no 24 volt power to the control, or a fault in the control; continuous flashing means the polarity of the 115 or 24 volt power is reversed RS6612012R8, pp. 44–45. The table has this kind of board for the GMSS9, GMES9, GMES80, GKS9, GMS8, GMH8, GMH95, GME95 and GME8 series and their Amana versions.
  • A three-color LED. On GMEC96 and GMEC80 boards the code is a color plus a number of repeating flashes. Green patterns and one or two amber flashes are normal operating states: solid green means the furnace is not receiving a call, and one amber flash is normal operation with a low stage call for heat. All red patterns are faults GMEC96: IOG-2011U, pp. 54–55; GMEC80: RS6621005R1, pp. 28–29. The 2019 service manuals for the Ultra-Low NOx MES96U and GMES80*U also use red, amber and green, with other meanings RS6612017, pp. 20–21; RS6621006, pp. 16–17. Their March 2023 revisions describe the same series with three-character codes RS6612017R4, p. 30; RS6621006R4, p. 33.
  • A three-character display. Newer boards show codes such as EE0, EE3 or EAF. IdL means idle, which is normal IOG-2037D, p. 43. On the Ultra-Low NOx GR9S96U and GR9S80U, 888 with all segments lit means the control is powering up RS6612302, p. 11; RS6621302, p. 10. When the display gives no signal, the tables point to power: the GR9S96 service manual’s symptom “LED display provides no signal” goes with no 115 volt power to the furnace or no 24 volt power to the control RS6612301, p. 37, and the current instructions word that row “nonE” IOG-2037D, p. 43.
  • Two characters on older ComfortNet boards. The tables for the GMVC9, GMVC8 and GMVC96 generations use codes such as E0, E3, d0 and b1, most of them with a matching message on a ComfortNet thermostat, for example E0 and LOCKOUT RS6612010R6, p. 47. These boards show OP or On while they wait for a call from the thermostat RS6612002, p. 48. The table on this page does not include the two-character codes. One edition of the owner’s manual adds that on a ComfortNet system a serious furnace fault makes the thermostat show “CALL FOR SERVICE” and scroll “CHECK FURNACE” HIG-2002, p. 8.

Read the code before you open anything or turn off the power. The GMES9 table notes that the LED flash code will cease if power to the control is interrupted through the disconnect or the door switch IOG-2020J, p. 40. The owner’s manual says an interlock switch keeps the furnace from operating when the blower door is not in place HIG-2002A, p. 6, and the current tables list an open door switch among the causes of the nonE row IOG-2037D, p. 43.

Why a flash count needs the series

The same count means different things on different boards. Four examples from Goodman’s tables; the single-LED column is the GMSS9 service manual, December 2017 revision (RS6612012R8, pp. 44–45; GMEC96: IOG-2011U, pp. 54–55; GMEC80: RS6621005R1, pp. 28–29; MES96U: RS6612017, pp. 20–21):

Flashes Single LED, GMSS9 Red LED, GMEC96 and GMEC80 Red LED, MES96U (2019 manual)
1 Lockout after 3 ignition retries “Flame sensed when no flame should be present” Lockout after 3 ignition attempts
3 “Pressure switch circuit not closed.” “Low fire pressure switch stuck open” “Inducer not making pressure setting.”
6 “Rollout limit circuit is open/Control board fuse open.” “Pressure switch cycling lockout, pressure switch has opened 5 times in the same heating cycle” “Burner temperature limit switch open.”
7 “Flame sense microamp signal is low.” “Lockout - excessive retries from flame not being proven during trial for ignition” “Gas valve circuit shorted.”

Revisions of the same manual differ too. The April 2019 GMES9 service manual lists 1 to 7 flashes RS6612016, pp. 43–44; the 2022 installation instructions for the same series go to 12, adding for example 8 flashes, “Igniter Relay Fault”, and 9 flashes, “Twinning Fault” IOG-2020J, pp. 41–42. The GMES80 changed the same way RS6621003, pp. 36–37; IOG-2021H, pp. 29–31, and the 2017 revision of the GMS8 manual adds 8 flashes RS6612006R7, p. 47. The Ultra-Low NOx furnaces have more than one colored-flash table: the 02/2022 installation instructions for the MES96U carry their own table, worded differently from the 2019 service manual IOG-2013F, pp. 33–34, and the 02/2022 instructions for the GMES80U also word some counts differently IOG-2019G, pp. 26–27. The “2019 manuals” rows on these pages come from the service manuals only. Three-character codes have variants as well: E11 is “Open rollout switch.” in the GR9S96 installation instructions and “Open burner box limit switch circuit.” in those for the Ultra-Low NOx GR9S96U IOG-2037D, p. 44; IOG-2040D, p. 39.

Finding the rows for your furnace

  1. Match the start of your model number to a series in the table. The series names come from the covers of Goodman’s service manuals and installation instructions.
  2. Use that series’ document. Goodman’s owner’s manual has no code list and says: “Refer to Installation Instructions for code identification.” HIG-2002A, p. 8
  3. Check the date. Tables change between revisions: the MES96U went from colored flashes to three-character codes (see above), and the 10/2026 installation instructions for the GR9S96 rewrote several corrective actions of the 09/2023 edition IOG-2037A, p. 43; IOG-2037D, pp. 44–45. Each row of the table names its document and page, and the document list on this page gives each revision.
  4. If your series is not in the table, these pages cannot tell you what your code means.

What the owner’s manual tells you to do

Goodman’s owner’s manuals list neither models nor codes, so these pages follow the Gas-Fired Warm Air Furnace User’s Information Manual HIG-2002A (09/19). Its section “Troubleshooting / Before you request a service call” asks for these checks, in this order HIG-2002A, p. 8:

  1. Look at the LED through the blower compartment sight glass. If it is flashing, record the number of flashes, shut the furnace down (next section) and contact a qualified servicer. If it is not flashing, go on.
  2. Check that the thermostat is set to HEAT and its temperature setting is above room temperature.
  3. Check the electrical panel for tripped circuit breakers or failed fuses, and reset the breakers or replace the fuses.
  4. Check for dirty filters at least once a month, and replace or clean them. The manual calls dirty filters the most common cause of improper furnace operation. Disconnect electrical power before removing filters HIG-2002A, p. 7.
  5. Check that return air and supply air grilles are not blocked by furniture, drapery, clothes or carpeting, and clear them.
  6. On high efficiency furnaces, check that the intake and vent terminations are not blocked.

Checks 2 to 6 are for a furnace whose LED is not flashing. The manual draws the line there: do not troubleshoot beyond these points and “Do not attempt repairs yourself” HIG-2002A, p. 8. It also says “do not remove any internal compartment covers”, because electrical components are in both compartments HIG-2002A, p. 6. Maintenance is for a qualified service technician, and the owner’s part is limited to frequent air filter changes HIG-2002A, p. 6. The warning in the manual’s filter section says to disconnect electrical power before removing filters or performing any other maintenance, and never to operate the furnace without a filter installed HIG-2002A, p. 7.

Other editions of the owner’s manual differ. HI-115C (02/12) and HIG-2002 (07/19) also ask you to check that the manual gas shut-off valve outside the furnace is ON, and if it is OFF, to turn the gas on by the start-up steps HI-115C, p. 8; HIG-2002, p. 8. HIG-2002 adds the ComfortNet thermostat check HIG-2002, p. 8. HIG-2001B (09/2019) has no sight-glass step HIG-2001B, p. 8. HIG-2005 (01/2020) has no troubleshooting section and says to contact a qualified service agency should the furnace ever fail to operate HIG-2005, p. 2.

Shutting the furnace down

The troubleshooting section sends you to the start-up section to shut the furnace down. The shut-down steps on the same page are HIG-2002A, p. 6:

  1. Set the thermostat to the lowest setting. The control closes the gas valve; the induced draft blower stops after 15 seconds and the circulator blower after a delay of 90, 120, 150 or 180 seconds.
  2. Remove the burner compartment door.
  3. Move the gas valve’s ON/OFF switch to OFF.
  4. Close the external manual gas shut-off valve.
  5. Replace the burner compartment door.

The safety label printed on page 9 of the manual calls this part the gas control lever. Use only your hand to push or turn it, never tools; if it will not move by hand, do not try to repair it, and call a qualified service technician HIG-2002A, p. 9. The shut-down list above does not turn off the electrical power. The label’s own shut-off steps do, before the gas control goes to OFF, if service is to be performed HIG-2002A, p. 9, and so do the start-up steps the troubleshooting section names HIG-2002A, p. 6. The manual’s maintenance warning is to disconnect electrical power before performing any service or maintenance HIG-2002A, p. 7.

Clearing a code

The owner’s manual gives one reset, for a lockout. It describes lockout as a non-functioning furnace, with the circulator blower possibly running continuously, “providing a diagnostic LED code” HIG-2002A, p. 6. On boards with a display, the GRVT96 instructions describe lockout as a non-functioning furnace with “an EE0 code displayed on the 7-segment display” IOG-2044B, p. 45. In Goodman’s tables, codes worded as a lockout include EE0, 1 flash on single-LED boards, and red 6, 7 and 8 flashes on GMEC96 and GMEC80 boards. The manual allows any of three methods HIG-2002A, p. 6:

  • Wait. The control resets itself and tries to resume normal operation after a one-hour lockout period.
  • Interrupt the 115 volt power to the furnace for more than 20 seconds.
  • Interrupt the thermostat signal to the furnace for between 0 and 20 seconds.

If the condition that caused the lockout is still there, the control locks out again. The manual says a furnace that locks out often has a problem that must be corrected, and to contact a qualified servicer HIG-2002A, p. 6.

Service and installation manuals give other times: 1 to 20 seconds for both the power and the thermostat methods in the GR9T96 instructions IOG-2038E, p. 46; more than 5 and less than 20 seconds at the thermostat, or at least 5 seconds at the disconnect, in the GMSS9 service manual RS6612012, p. 31. The GMVC96*BA service manual describes the thermostat method as lowering the thermostat until there is no call for heat for 1 to 20 seconds, then setting it back RS6612014, p. 72. These pages give the owner’s manual times.

Boards with a three-character display also keep a list of past faults, “Last 10 Faults” in the board’s menu RS6612301, p. 34. Viewing and erasing it is done with the buttons on the control board and is described in the installation instructions IOG-2037D, p. 45; these pages do not repeat it.

When to stop and call a professional

The owner’s manual says installation and service must be performed by a qualified installer, service agency or the gas supplier HIG-2002A, p. 1. Goodman’s service manual adds that in jurisdictions that require licenses, only licensed personnel should service the equipment RS6612301, p. 1. Stop and call when:

  • You smell gas. The steps from the cover of the owner’s manual are at the top of every code page HIG-2002A, p. 1. Some Goodman documents print a different block: HIG-2005 adds “Leave the building immediately.” HIG-2005, p. 1, and the English blocks in IOG-2032C and IOG-2013F are written for a vehicle IOG-2032C, p. 3; IOG-2013F, p. 3. In HIG-2002A itself, the French version of the block includes leaving the building and the English version does not HIG-2002A, p. 1. For propane, the manual asks for a gas detecting warning device, because the odorant can fade HIG-2002A, p. 5.
  • The furnace overheats or the gas supply does not shut off. Turn off the manual gas shutoff valve outside the furnace before you turn off the electrical supply HIG-2002A, p. 2.
  • Any part of the furnace has been under water. Do not use it; the label says to have a qualified service technician inspect it and replace any part of the control system and any gas control that was under water HIG-2002A, p. 9.
  • The LED is flashing a code, or a lockout keeps coming back HIG-2002A, pp. 6, 8.
  • The work goes past the filter HIG-2002A, p. 6.

Carbon monoxide: the manual’s warning is at the top of every code page HIG-2002A, p. 4. The manual also lists air starvation signals that indicate conditions that may produce carbon monoxide, or that carbon monoxide may be present: headaches, nausea, dizziness or flu-like symptoms; excessive humidity, heavily frosted windows or a moist, clammy feeling in the home; smoke from a fireplace that will not draw up the chimney; flue gases that will not draw up the vent pipe HIG-2002A, p. 4. It gives no separate step for these signs. Its general warning is to contact a qualified servicer at once if an abnormal condition is noticed HIG-2002A, p. 6.

See also

Other gas furnaces: Carrier, Lennox, Rheem and Ruud

Goodman is a trademark of its owner. How House Works is not affiliated with or endorsed by Goodman.

Sources

  1. Goodman Manufacturing. Gas-Fired Warm Air Furnace User's Information Manual. HIG-2002A, 09/19. Accessed Oct 17, 2026.
  2. Goodman Manufacturing. Gas-Fired Warm Air Furnace User's Information Manual. HIG-2002, 07/19. Accessed Oct 17, 2026.
  3. Goodman Manufacturing. GAS-FIRED WARM AIR FURNACE USER'S INFORMATION MANUAL. HIG-2001B, 09/2019. Accessed Oct 17, 2026.
  4. Goodman Manufacturing. Gas-Fired Warm Air Furnace (owner’s manual). HIG-2005, 01/2020. Accessed Oct 17, 2026.
  5. Goodman Manufacturing. GAS-FIRED WARM AIR FURNACE USER'S INFORMATION MANUAL. HI-115C, 02/12. Accessed Oct 17, 2026.
  6. Goodman Manufacturing. Service manual: 34.5" Chassis ACVC96/AMVC96 GCVC96/GMVC96 Gas Furnaces. RS6612010R6, November 2017. Accessed Oct 19, 2026.
  7. Goodman Manufacturing. Service manual: GMVC9, GCVC9, AMVC9, ACVC9 Gas Furnaces & Accessories. RS6612002, February 2013. Accessed Oct 17, 2026.
  8. Goodman Manufacturing. Service manual: Goodman Brand GMEC96 & Amana Brand AMEC96 Two Stage Furnace with multi-speed ECM Motor. RS6612013, August 2014. Accessed Oct 17, 2026.
  9. Goodman Manufacturing. Installation Instructions for *MES96*U Ultra Low NOx Gas Furnace. IOG-2013F, 02/2022. Accessed Oct 17, 2026.
  10. Goodman Manufacturing. Installation Instructions for *MES80 Ultra Low NOx Gas Furnace. IOG-2019G, 02/2022. Accessed Oct 19, 2026.
  11. Goodman Manufacturing. Installation Instructions for *DVT96* & *RVT96* Two-Stage Gas Furnace. IOG-2044B, 10/2026. Accessed Oct 17, 2026.
  12. Goodman Manufacturing. Installation Instructions for *MES9* & *CES9* Single-Stage Gas Furnace. IOG-2020J, 04/2022. Accessed Oct 19, 2026.
  13. Goodman Manufacturing. Installation Instructions for *R9S96/*D9S96 & *R9S92 Single-Stage Gas Furnace. IOG-2037D, 10/2026. Accessed Oct 17, 2026.
  14. Goodman Manufacturing. Installation Instructions for *R9S96*U Ultra Low NOx Gas Furnace. IOG-2040D, 08/2026. Accessed Oct 17, 2026.
  15. Goodman Manufacturing. Installation Instructions for *R9S80 & *D9S80* Gas Furnace. IOG-2035D, 09/2026. Accessed Oct 17, 2026.
  16. Goodman Manufacturing. Installation Instructions for *R9S80*U Ultra Low NOx Gas Furnace. IOG-2039F, 10/2026. Accessed Oct 17, 2026.
  17. Goodman Manufacturing. Installation Instructions for VR9S96*U Ultra Low NOx Gas Furnace. IOG-2050A, 08/2026. Accessed Oct 17, 2026.
  18. Goodman Manufacturing. Installation Instructions for *R9T96 & *D9T96 Two-Stage Gas Furnaces. IOG-2038E, 07/2026. Accessed Oct 17, 2026.
  19. Goodman Manufacturing. Installation Instructions for *R9T80 & *D9T80* Gas Furnace. IOG-2036D, 09/2026. Accessed Oct 17, 2026.
  20. Goodman Manufacturing. Installation Instructions for *RVT80* & *DVT80* Gas Furnace. IOG-2043B, 10/2026. Accessed Oct 17, 2026.
  21. Goodman Manufacturing. Installation Instructions for *DVM97* & *RVM97* Modulating Gas Furnace. IOG-2045A, 08/2026. Accessed Oct 17, 2026.
  22. Goodman Manufacturing. Installation Instructions for *RVS96 & *DVS96 Ultra Low NOx Variable Speed Gas Furnace. IOG-2042A, 09/2026. Accessed Oct 17, 2026.
  23. Goodman Manufacturing. Service manual: Goodman Brand GM9C80/GC9C80 & Amana Brand AM9C80/AC9C80 Two Stage Furnace with nine speed ECM Motor. RS6621007R3, September 2026. Accessed Oct 19, 2026.
  24. Goodman Manufacturing. Service manual: 34.5" Chassis ACVC96*BB/AMVC96*BB/GCVC96*BB/GMVC96*BB Gas Furnaces. RS6612023R2, November 2026. Accessed Oct 19, 2026.
  25. Goodman Manufacturing. Service manual: 34.5" Chassis ACVC96*BA/AMVC96*BA GCVC96*BA/GMVC96*BA Gas Furnaces (BA revision & above). RS6612014R3, October 2020. Accessed Oct 19, 2026.
  26. Goodman Manufacturing. Service manual: ACVC80*AC/AMVC80*AC & GCVC80*AC/GMVC80*AC Gas Furnaces. RS6621009R1, March 2023. Accessed Oct 19, 2026.
  27. Goodman Manufacturing. Service manual: 34.5" Chassis ACVM97*BA/AMVM97*BA GCVM97*BA/GMVM97*BA Modulating Gas Furnaces (BA revision & above). RS6612015R8, March 2023. Accessed Oct 19, 2026.
  28. Goodman Manufacturing. Installation Instructions for *R9S96/*D9S96 & *R9S92 Single-Stage Gas Furnace. IOG-2037A, 09/2023. Accessed Oct 17, 2026.
  29. Goodman Manufacturing. Service manual: 96% Single Stage Ultra-Low NOx Gas Furnaces A/GR9S96*U*. RS6612302, January 2025. Accessed Oct 17, 2026.
  30. Goodman Manufacturing. Service manual: 80% Single Stage Ultra-Low NOx Gas Furnaces A/GR9S80*U*. RS6621302, October 2024. Accessed Oct 17, 2026.
  31. Goodman Manufacturing. Service manual: GR9S92 / GR9S96 / GD9S96 / AR9S92 / AR9S96 / AD9S96 / VM9S96 / VC9S96 Single Stage Gas Furnaces and Accessories. RS6612301, May 2024. Accessed Oct 17, 2026.
  32. Goodman Manufacturing. Service manual: Goodman Brand GR9T96/GD9T96 & Amana Brand AR9T96/AD9T96 Two Stage Furnace with Nine speed ECM Motor. RS6612304, May 2024. Accessed Oct 17, 2026.
  33. Goodman Manufacturing. Service manual: Goodman Brand GR9T80/GD9T80 & Amana Brand AR9T80/AD9T80 Two Stage Furnace with Nine Speed ECM Motor. RS6621304, December 2023. Accessed Oct 17, 2026.
  34. Goodman Manufacturing. Installation Instructions for *M9S96/*C9S96 & *M9S92 Single-Stage Gas Furnace. IOG-2029D, 07/2023. Accessed Oct 17, 2026.
  35. Goodman Manufacturing. Installation Instructions for *M9S80 & *C9S80* Gas Furnace. IOG-2030B, 04/2022. Accessed Oct 17, 2026.
  36. Goodman Manufacturing. Installation Instructions for *M9C96 & *C9C96 Two-Stage Gas Furnaces. IOG-2027E, 07/2023. Accessed Oct 17, 2026.
  37. Goodman Manufacturing. Installation Instructions for *M9C80 & *C9C80* Gas Furnace. IOG-2026B, 04/2022. Accessed Oct 17, 2026.
  38. Goodman Manufacturing. Installation Instructions for *CVC96*BB & *MVC96*BB Two-Stage Gas Furnace. IOG-2015L, 06/2023. Accessed Oct 19, 2026.
  39. Goodman Manufacturing. Installation Instructions for *MVC8*CA & *CVC8*CA Gas Furnace. IOG-2016A, 07/2019. Accessed Oct 17, 2026.
  40. Goodman Manufacturing. Installation Instructions for *CVM97*B* & *MVM97*B* Modulating Gas Furnace. IOG-2017H, 07/2023. Accessed Oct 19, 2026.
  41. Goodman Manufacturing. Installation Instructions for CCVS96 Ultra Low NOx Variable Speed Gas Furnace. IOG-2034A, 6/2023. Accessed Oct 17, 2026.
  42. Goodman Manufacturing. Installation Instructions for *M9S96*U Ultra Low NOx Gas Furnace. IOG-2032C, 07/2023. Accessed Oct 17, 2026.
  43. Goodman Manufacturing. Service manual: *MES96*U Single Stage Ultra-Low NOx Gas Furnaces and Accessories. RS6612017R4, March 2023. Accessed Oct 19, 2026.
  44. Goodman Manufacturing. Service manual: 80% Single Stage Ultra-Low NOx Gas Furnaces GMES80*U* & AMES80*U* & Accessories. RS6621006R4, March 2023. Accessed Oct 19, 2026.
  45. Goodman Manufacturing. Service manual: Goodman Brand GRVT80/GDVT80 & Amana Brand ARVT80/ADVT80 80% Two Stage Gas Furnaces with Variable-Speed ECM Motor. RS6621305, January 2025. Accessed Oct 17, 2026.
  46. Goodman Manufacturing. Installation Instructions for *MVC80* & *CVC80* Gas Furnace. IOG-2023E, 07/2022. Accessed Oct 17, 2026.
  47. Goodman Manufacturing. Installation Instructions for VR9S96 & VD9S96 Single-Stage Gas Furnace. IOG-2049, 4/2026. Accessed Oct 17, 2026.
  48. Goodman Manufacturing. Service manual: *RVS80*U Single Stage Variable Speed Ultra-Low NOx Gas Furnaces and Accessories. RS6621303, April 2025. Accessed Oct 17, 2026.
  49. Goodman Manufacturing. Service manual: Goodman Brand GRVT96/GDVT96 & Amana Brand ARVT96/ADVT96 96% Two Stage Gas Furnaces with Variable-Speed ECM Motor. RS6612305, April 2025. Accessed Oct 17, 2026.
  50. Goodman Manufacturing. Service manual: Goodman Brand GRVM97/GDVM97 & Amana Brand ARVM97/ADVM97 97% Modulating Gas Furnaces with Variable-Speed ECM Motor. RS6612306, April 2025. Accessed Oct 17, 2026.
  51. Goodman Manufacturing. Installation Instructions for Gas Variable Speed Furnace. IOG-2033A, 05/2023. Accessed Oct 17, 2026.
  52. Goodman Manufacturing. Service manual: 34.5" Chassis ACVM97*BA/AMVM97*BA GCVM97*BA/GMVM97*BA Modulating Gas Furnaces (BA revision & above). RS6612015, October 2018. Accessed Oct 17, 2026.
  53. Goodman Manufacturing. Service manual: 34.5" Chassis ACVC96*BA/AMVC96*BA GCVC96*BA/GMVC96*BA Gas Furnaces (BA revision & above). RS6612014, December 2017. Accessed Oct 17, 2026.
  54. Goodman Manufacturing. Installation Instructions for *CVC96*BB & *MVC96*BB Two-Stage Gas Furnace. IOG-2015F, 10/2020. Accessed Oct 17, 2026.
  55. Goodman Manufacturing. Installation Instructions for *CVM97*B* & *MVM97*B* Modulating Gas Furnace. IOG-2017F, 07/2022. Accessed Oct 17, 2026.
  56. Goodman Manufacturing. Installation Instructions for *MVS96 Ultra Low NOx Variable Speed Gas Furnace. IOG-2025G, 06/2023. Accessed Oct 19, 2026.
  57. Goodman Manufacturing. Service manual: 80% Single Stage Gas Furnaces GR9S80, AR9S80, GD9S80, AD9S80, VR9S80, VD9S80 & Accessories. RS6621301, November 2023. Accessed Oct 17, 2026.
  58. Goodman Manufacturing. Service manual: *MVS80*U Single Stage Variable Speed Ultra-Low NOx Gas Furnaces and Accessories. RS6612019R3, June 2023. Accessed Oct 19, 2026.
  59. Goodman Manufacturing. Service manual: 34.5" Chassis ACVC96*BB/AMVC96*BB/GCVC96*BB/GMVC96*BB Gas Furnaces. RS6612023, January 2021. Accessed Oct 17, 2026.
  60. Goodman Manufacturing. Service manual: GR9S92 / GR9S96 / GD9S96 / AR9S92 / AR9S96 / AD9S96 / VM9S96 / VC9S96 Single Stage Gas Furnaces and Accessories. RS6612301R2, March 2026. Accessed Oct 19, 2026.
  61. Goodman Manufacturing. Service manual: *RVS96*U & CDVS96*U Single Stage Variable Speed Ultra-Low NOx Gas Furnaces and Accessories. RS6612303, May 2025. Accessed Oct 17, 2026.
  62. Goodman Manufacturing. Installation Instructions for *MES80 / *CES80 Gas Furnace. IOG-2021H, 02/2022. Accessed Oct 19, 2026.
  63. Goodman Manufacturing. Installation Instructions for *MSS9* & *CSS9* Single-Stage Gas Furnace. IOG-2009Q, 08/2022. Accessed Oct 19, 2026.
  64. Goodman Manufacturing. Service manual: GKS9 / AKSS92 Single Stage Up-Flow Gas Furnaces and Accessories. RS6612004R2, November 2014. Accessed Oct 19, 2026.
  65. Goodman Manufacturing. Service manual: Goodman & Amana Brand 80% Single Stage Gas Furnaces GMS8, AMS8, GDS8, ADSS8 & Accessories. RS6612006R7, November 2017. Accessed Oct 19, 2026.
  66. Goodman Manufacturing. Service manual: 33 3/8" 80% Modified Two Stage Gas Furnaces AMH8, GMH8, GDH8, ADSH8 & Accessories. RS6612007R4, July 2018. Accessed Oct 19, 2026.
  67. Goodman Manufacturing. Service manual: Goodman Brand & Amana Brand 96% Modified Two Stage Furnace GMH95, AMH95, GCH95, ACSH96. RS6612003R2, November 2014. Accessed Oct 19, 2026.
  68. Goodman Manufacturing. Service manual: Goodman Brand GME95 & Amana Brand AMEH96 Modified Two Stage Furnace with EEM Motor. RS6612005R1, November 2014. Accessed Oct 19, 2026.
  69. Goodman Manufacturing. Service manual: GME8 & AMEH8 Modified Two Stage Furnace with EEM Motor. RS6621001R2, August 2016. Accessed Oct 19, 2026.
  70. Goodman Manufacturing. Service manual: Goodman & Amana Brand 80% Single Stage Gas Furnaces GMS8, AMS8, GDS8, ADSS8 & Accessories. RS6612006, July 2013. Accessed Oct 17, 2026.
  71. Goodman Manufacturing. Service manual: 80% Single Stage Gas Furnaces GMES80, AMES80, GCES80, ACES80, VMES80, VCES80 & Accessories. RS6621003, April 2019. Accessed Oct 17, 2026.
  72. Goodman Manufacturing. Service manual: GMSS9*/GCSS9*/AMSS9*/ACSS9* Single Stage Gas Furnaces and Accessories. RS6612012, August 2014. Accessed Oct 17, 2026.
  73. Goodman Manufacturing. Service manual: GMES9*/GCES9*/AMES9*/ACES9* VMES9*/VCES9* Single Stage Gas Furnaces and Accessories. RS6612016, April 2019. Accessed Oct 17, 2026.
  74. Goodman Manufacturing. Service manual: GMSS9*/GCSS9*/AMSS9*/ACSS9* Single Stage Gas Furnaces and Accessories. RS6612012R8, December 2017. Accessed Oct 19, 2026.
  75. Goodman Manufacturing. Installation Instructions for *MEC96 Upflow / Horizontal Two-Stage Gas Furnace. IOG-2011U, 02/2022. Accessed Oct 19, 2026.
  76. Goodman Manufacturing. Service manual: Goodman Brand GMEC80/GCEC80 & Amana Brand AMEC80/ACEC80 Two Stage Furnace with multi-speed ECM Motor. RS6621005R1, June 2020. Accessed Oct 19, 2026.
  77. Goodman Manufacturing. Service manual: *MES96*U Single Stage Ultra-Low NOx Gas Furnaces and Accessories. RS6612017, October 2019. Accessed Oct 17, 2026.
  78. Goodman Manufacturing. Service manual: 80% Single Stage Ultra-Low NOx Gas Furnaces GMES80*U* & AMES80*U* & Accessories. RS6621006, October 2019. Accessed Oct 17, 2026.